8 Application Steps
8.1 Optimize Image
45
8
Test
This function can actually test for reading codes by using created settings.
Additionally, the number of trigger input can be set by using "Trigger On" and "Trigger Off" in the drop-down window of the
[Test] button.
Note: The image transmission may be disabled when codes are read at high-speed because the speed may be limited by
reading settings, codes to be read, or a connection interface.
Trigger On
Trigger Off
Trigger occurrence frequency
20 ms
1980 ms
0.5 times (0.5 Hz) per second
20 ms
980 ms
1 time (1 Hz) per second
20 ms
480 ms
2 times (1 Hz) per second
20 ms
180 ms
5 times (1 Hz) per second
20 ms
80 ms
10 times (1 Hz) per second
Summary of Contents for Melsensor CF26-LR
Page 2: ......
Page 11: ...1 OVERVIEW 1 1 Overview of DataMan Setup Tool for MELSENSOR 9 1 MEMO ...
Page 13: ...2 SetupTool INSTALLATION 2 1 Installation 11 2 MEMO ...
Page 15: ...3 CODE READER SETUP FLOW CHART 3 1 Setup Flow Chart 13 3 MEMO ...
Page 17: ...4 CONFIGURATIONS 4 1 Configuration and Wiring of CF26 CF37 Series 15 4 MEMO ...
Page 92: ...90 APPX Appendix 5 Supplemental Remarks for Tuning 2 MEMO ...
Page 111: ......