Part 5: Review on Replacement of MR-J2S-30 kW or Higher Capacity Models with MR-J4-DU_
5 - 31
4.2 Inrush Current When Turning On the Main Circuit/Control Circuit Power Supply
POINT
Inrush current values are changeable depending on the frequency of turning
on/off the power supplies and ambient temperature.
An inrush current flow in the units at power-on. Use a molded-case circuit breaker and a magnetic contactor
to protect the units from the inrush current. (Refer to Section 5.3)
When using a circuit protector, it is recommended that you use an inertia delay type which will not be tripped
by the inrush current.
When the converter unit and drive unit are connected by daisy chain, the total inrush current of the both units
flows in.
1) MR-J2S series inrush current when turning on the main circuit/control circuit power supply
The table below shows inrush currents (references) when the maximum permissible voltage (200 V AC
class: 253 V AC, 400 V AC class: 528 V AC) is applied. The power supply capacity is 2500 kVA and the
wiring length is 1 m.
Converter unit
Servo amplifier
Inrush current (A
0-P
)
Main circuit power supply (L
1
/L
2
/L
3
)
Control circuit power supply (L
11
/L
21
)
MR-HP30KA
MR-J2S-30K
_
270 A
(Attenuates to approximately 20 A in 160 ms)
7 A
(Attenuates to approximately 0 A in 200 ms)
MR-J2S-37K
_
MR-HP55KA4
MR-J2S-30K
_
4
554 A
(Attenuates to approximately 20 A in 80 ms)
15 A
(Attenuates to approximately 0 A in 150 ms)
MR-J2S-37K
_
4
555 A
(Attenuates to approximately 20 A in 100 ms)
MR-J2S-45K
_
4
556 A
(Attenuates to approximately 20 A in 100 ms)
MR-J2S-55K
_
4
2) MR-J4 series inrush current when turning on the main circuit/control circuit power supply
The table below shows inrush currents (references) when the maximum permissible voltage (200 V AC
class: 240 V AC, 400 V AC class: 480 V AC) is applied. The power supply capacity is 2500 kVA and the
wiring length is 1 m.
Converter unit
Servo amplifier
Inrush current (A
0-P
)
Main circuit power supply (L
1
/L
2
/L
3
)
Control circuit power supply (L
11
/L
21
)
MR-CR55K
MR-J4-DU30K_
154 A
(Attenuates to approximately 20 A in 150 ms)
31 A
(Attenuates to approximately 2 A in 60 ms)
MR-J4-DU37K_
MR-CR55K4
MR-J4-DU30K_4
305 A
(Attenuates to approximately 20 A in 70 ms)
27 A
(Attenuates to approximately 2 A in 45 ms)
MR-J4-DU37K_4
MR-J4-DU45K_4
MR-J4-DU55K_4
Summary of Contents for MELSERVO-J2-Super Series
Page 18: ...Part 1 Summary of MR J2S MR J2M Replacement 1 1 Part 1 Summary of MR J2S MR J2M Replacement ...
Page 31: ...Part 1 Summary of MR J2S MR J2M Replacement 1 14 MEMO ...
Page 109: ...Part 3 Review on Replacement of MR J2S _B_ with MR J4 _B_ 3 32 MEMO ...
Page 161: ...Part 4 Review on Replacement of MR J2S _CP_ CL_ with MR J4 _A_ RJ 4 52 MEMO ...
Page 239: ...Part 6 Review on Replacement of MR J2M with MR J4 6 20 MEMO ...
Page 240: ...Part 7 Common Reference Material 7 1 Part 7 Common Reference Material ...
Page 284: ...Part 7 Common Reference Material 7 45 Click Update Project ...
Page 342: ...Part 8 Review on Replacement of Motor 8 1 Part 8 Review on Replacement of Motor ...
Page 409: ...Part 8 Review on Replacement of Motor 8 68 MEMO ...
Page 461: ...Part 9 Review on Replacement of Optional Peripheral Equipment 9 52 MEMO ...
Page 462: ...Part 10 Startup Procedure Manual 10 1 Part 10 Startup Procedure Manual ...