9 USING FUNCTIONAL SAFETY [G] [WG]
9.7 Wiring the SBC output
307
9
9.7
Wiring the SBC output
This function only guarantees that the power supply for the mechanical brake is correct. It cannot detect brake
wear. Check the mechanical brake periodically to ensure it is functioning correctly.
To use SBCS (SBC output), connect it to the electromagnetic brake of the servo motor. Wire the system so that the
electromagnetic brake activates when SBCS (SBC output) turns off. There is no need to use the MBR (Electromagnetic brake
interlock) of the servo amplifier. For information on the operating sequence when using the SBC function, refer to "SBC
function" in the following manual.
*1 Configure a circuit which interlocks with an emergency stop switch to shut off.
*2 Do not use the 24 V DC interface power supply for the electromagnetic brake.
SDOB
B2
B1
RA2
U
B
*1
RA1
SDOCOM
SDOA
CN8
RA1
RA2
ALM
Servo amplifier
24 V DC
Servo motor
24 V DC
*2
(Malfunction)