11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 16
11.5 Selection example of wires
POINT
To comply with the UL/CSA standard, use the wires shown in appendix 2 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection conditions of wire size is as follows.
Construction condition: One wire is constructed in the air.
Wiring length: 30 m or shorter
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
3) Regenerative option lead
Regenerative option
C
P+
L1
L2
L3
1) Power lead
Power supply
Servo amplifier
U
V
W
2) Servo motor power supply lead
M
Table 11.1 shows examples for using the 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV
wire).
Table 11.1 Wire size selection example (HIV wire)
Wire [mm
2
]
Servo amplifier
1) L1/L2/L3/
3) P+•C
2) U/V/W/
(Note 1)
MR-JE-10A
MR-JE-20A
MR-JE-40A
MR-JE-70A
2 (AWG 14)
2 (AWG 14)
AWG 18 to 14
(Note 2)
MR-JE-100A
MR-JE-200A
MR-JE-300A
3.5 (AWG 12)
AWG 16 to 10
Note 1. The wire size shows applicable size of the servo amplifier connector. For wires
connecting to the servo motor, refer to "HF-KN/HF-SN Servo Motor Instruction
Manual".
2. Be sure to use the size of 2 mm
2
when corresponding to UL/CSA standard.
Summary of Contents for MELSERVO-JE MR-JE-100A
Page 23: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO ...
Page 29: ...2 INSTALLATION 2 6 MEMO ...
Page 91: ...3 SIGNALS AND WIRING 3 62 MEMO ...
Page 171: ...5 PARAMETERS 5 44 MEMO ...
Page 195: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 221: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 26 MEMO ...
Page 249: ...8 TROUBLESHOOTING 8 28 MEMO ...
Page 255: ...9 DIMENSIONS 9 6 MEMO ...
Page 263: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 293: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 30 MEMO ...