3. SIGNALS AND WIRING
(2) Output signals
Control
mode
Signal
Symbol
Connector
pin No.
Functions/Applications
I/O
division
P S T
Trouble
ALM
CN1B
18
ALM turns off when power is switched off or the protective circuit
is activated to shut off the base circuit.
Without alarm occurring, ALM turns on within about 1s after
power-on.
DO-1
Dynamic brake
interlock
DB
This signal can be used with the 11kW or more servo amplifier.
When using this signal, set " 1 " in parameter No. 1.
When the dynamic brake is operated, DB turns off. (Refer to
section 13.1.4.)
DO-1
Ready
RD
CN1A
19
RD turns on when the servo is switched on and the servo
amplifier is ready to operate.
DO-1
In position
INP
INP turns on when the number of droop pulses is in the preset in-
position range. The in-position range can be changed using
parameter No. 5.
When the in-position range is increased, INP-SG may be kept
connected during low-speed rotation.
DO-1
Speed reached
SA
CN1A
18
SA turns on when the servo motor speed has nearly reached the
preset speed. When the preset speed is 20r/min or less, SA
always turns on. SA does not turn on even when the servo on
(SON) is turned off or the servo motor speed by the external force
reaches the preset speed while both the forward rotation start
(ST1) and the reverse rotation start (ST2) are off.
DO-1
Limiting speed
VLC
VLC turns on when speed reaches the value limited using any of
the internal speed limits 1 to 7 (parameter No. 8 to 10, 72 to 75)
or the analog speed limit (VLA) in the torque control mode.
VLC turns off when servo on (SON) turns off.
DO-1
Limiting torque
TLC
CN1B
6
TLC turns on when the torque generated reaches the value set to
the internal torque limit 1 (parameter No. 28) or analog torque
limit (TLA).
DO-1
Zero speed
ZSP
CN1B
19
ZSP turns on when the servo motor speed is zero speed (50r/min)
or less. Zero speed can be changed using parameter No. 24.
DO-1
Electromagnetic
brake interlock
MBR
CN1B
19
Set " 1 " in parameter No. 1 to use this parameter. Note that
ZSP will be unusable.
MBR turns off when the servo is switched off or an alarm occurs.
DO-1
Warning
WNG
To use this signal, assign the connector pin for output using
parameter No.49. The old signal before assignment will be
unusable.
When warning has occurred, WNG turns on.
When there is no warning, WNG turns off within about 1s after
power-on.
DO-1
Battery warning BWNG
To use this signal, assign the connector pin for output using
parameter No.49. The old signal before assignment will be
unusable.
BWNG turns on when battery cable breakage warning (AL. 92) or
battery warning (AL. 9F) has occurred.
When there is no battery warning, BWNG turns off within about
1s after power-on.
DO-1
Summary of Contents for MR-J2S-*A
Page 13: ...WWW NNC IR A 12 MEMO ...
Page 117: ...WWW NNC IR 3 70 3 SIGNALS AND WIRING MEMO ...
Page 185: ...WWW NNC IR 7 12 7 GENERAL GAIN ADJUSTMENT MEMO ...
Page 195: ...WWW NNC IR 8 10 8 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 197: ...WWW NNC IR 9 2 9 INSPECTION MEMO ...
Page 221: ...WWW NNC IR 11 10 11 OUTLINE DIMENSION DRAWINGS MEMO ...
Page 293: ...WWW NNC IR 13 64 13 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...
Page 321: ...WWW NNC IR 14 28 14 COMMUNICATION FUNCTIONS MEMO ...
Page 389: ...WWW NNC IR 15 68 15 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...