17. APPLICATION OF FUNCTIONS
17 - 62
2) Instantaneous power failure time of control circuit power supply < [Pr. PX28 SEMI-F47 function -
Instantaneous power failure detection time]
Operation status differs depending on how bus voltage decrease.
a) When the bus voltage decreases lower than Undervoltage level within the instantaneous
power failure time of the control circuit power supply
[AL. 10 Undervoltage] occurs when the bus voltage decrease lower than Undervoltage level
regardless of the enabled instantaneous power failure tough drive.
[Pr. PX28]
Instantaneous power failure time of the control circuit power supply
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Bus voltage
Undervoltage level
(Note)
ALM
(Malfunction)
MTTR
(During tough drive)
MBR
(Electromagnetic
brake interlock)
Base circuit
WNG
(Warning)
Control circuit
power supply
ON (energization)
OFF (power failure)
Note. Refer to table 17.8 for the undervoltage level.