11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 27
11.5 Selection example of wires
POINT
Refer to section 11.1.2 for SSCNET III cable.
To comply with the EC/EN/UL/CSA standard, use the wires shown in app. 4 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection conditions of wire size are as follows.
Construction condition: One wire is constructed in the air
Wire length: 30 m or less
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
3) Regenerative option lead
Regenerative option
Servo amplifier
2) Control circuit power supply lead
D
C
P+
L1
L2
L3
L11
L12
1) Main circuit power supply lead
Power supply
U
V
W
M
4) Servo motor power supply lead