11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 18
11.5 Selection example of wires
POINT
To comply with the IEC/EN/UL/CSA standard, use the wires shown in app. 2 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection conditions of wire size are as follows.
Construction condition: Single wire set in midair
Wiring length: 30 m or shorter
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
3) Regenerative option lead
Regenerative option
C
P+
L1
L2
L3
1) Power lead
Power supply
Servo amplifier
U
V
W
2) Servo motor power supply lead
M
Table 11.1 shows examples for using the 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV
wire).
Table 11.1 Wire size selection example (HIV wire)
Servo amplifier
Wire
[mm
2
]
1) L1/L2/L3/
3) P+
/
C
2) U
/
V
/
W
/
(Note 1)
MR-JE-10A
MR-JE-20A
AWG 18 to 14
(Note 2)
MR-JE-40A
MR-JE-70A
2 (AWG 14)
2 (AWG 14)
MR-JE-100A
MR-JE-200A
(3-phase power
supply input)
AWG 16 to 10
MR-JE-200A
(1-phase power
supply input)
3.5 (AWG 12)
MR-JE-300A
2 (AWG 14)
Note 1. The wire size shows applicable size of the servo amplifier connector. For wires
connecting to the servo motor, refer to "HG-KN/HG-SN Servo Motor Instruction
Manual".
2. Be sure to use the size of 2 mm
2
when corresponding to IEC/EN/UL/CSA
standard.
Summary of Contents for MR-JE-_A
Page 9: ...A 8 MEMO ...
Page 15: ...6 MEMO ...
Page 29: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Page 139: ...4 STARTUP 4 38 MEMO ...
Page 187: ...5 PARAMETERS 5 48 MEMO ...
Page 221: ...6 NORMAL GAIN ADJUSTMENT 6 34 MEMO ...
Page 259: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 265: ...9 DIMENSIONS 9 6 MEMO ...
Page 273: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 339: ...12 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 12 34 MEMO ...