3. SIGNALS AND WIRING
3 - 28
(b) Output device
Device Symbol
Connector
pin No.
Function and application
I/O
division
Control
mode
P S T
Malfunction
ALM
CN1-48 When an alarm occurs, ALM will turn off.
When an alarm does not occur, ALM will turn on after 2.5 s to 3.5 s after
power-on.
When [Pr. PD34] is "_ _ 1 _", an alarming or warning will turn off ALM.
DO-1
Ready
RD
CN1-49 Enabling servo-on to make the servo amplifier ready to operate will turn on
RD.
DO-1
In-position
INP
CN1-24 When the number of droop pulses is in the preset in-position range, INP
will turn on. The in-position range can be changed using [Pr. PA10]. When
the in-position range is increased, INP may be on during low-speed
rotation.
INP turns on when servo-on turns on.
DO-1
Speed reached
SA
When the servo motor speed reaches the following range, SA will turn on.
Set speed ± ((Set speed × 0.05) + 20) r/min
When the preset speed is 20 r/min or less, SA always turns on.
SA does not turn on even when the SON (Servo-on) is turned off or the
servo motor speed by the external force reaches the preset speed while
both ST1 (Forward rotation start) and ST2 (reverse rotation start) are off.
DO-1
Limiting speed
VLC
VLC turns on when speed reaches a value limited with any of [Pr. PC05
Internal speed limit 1] to [Pr. PC11 Internal speed limit 7] or VLA (Analog
speed limit).
This turns off when SON (Servo-on) turns off.
DO-1
Limiting torque
TLC
TLC turns on when a generated torque reaches a value set with any of [Pr.
PA11 Forward torque limit], [Pr. PA12 Reverse torque limit], or TLA
(Analog torque limit).
DO-1
Zero speed
detection
ZSP
CN1-23 ZSP turns on when the servo motor speed is zero speed (50 r/min) or less.
Zero speed can be changed with [Pr. PC17].
OFF
ON
Servo motor
speed
20 r/min
(Hysteresis width)
[Pr. PC17]
20 r/min
(Hysteresis width)
OFF level
-70 r/min
ON level
-50 r/min
ON level
50 r/min
OFF level
70 r/min
0 r/min
[Pr. PC17]
ZSP
(Zero speed
detection)
1)
3)
2)
4)
Forward
rotation
direction
Reverse
rotation
direction
ZSP will turn on when the servo motor is decelerated to 50 r/min (at 1)),
and will turn off when the servo motor is accelerated to 70 r/min again (at
2)).
ZSP will turn on when the servo motor is decelerated again to 50 r/min (at
3)), and will turn off when the servo motor speed has reached -70 r/min (at
4)).
The range from the point when the servo motor speed has reached on
level, and ZSP turns on, to the point when it is accelerated again and has
reached off level is called hysteresis width.
Hysteresis width is 20 r/min for this servo amplifier.
DO-1
Electromagnetic
brake interlock
MBR
When using the device, set operation delay time of the electromagnetic
brake in [Pr. PC16].
When a servo-off status or alarm occurs, MBR will turn off.
DO-1
Warning
WNG
When warning has occurred, WNG turns on. When a warning is not
occurring, WNG will turn off in 2.5 s to 3.5 s after power-on.
DO-1
Summary of Contents for MR-JE-_A
Page 9: ...A 8 MEMO ...
Page 15: ...6 MEMO ...
Page 29: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Page 139: ...4 STARTUP 4 38 MEMO ...
Page 187: ...5 PARAMETERS 5 48 MEMO ...
Page 221: ...6 NORMAL GAIN ADJUSTMENT 6 34 MEMO ...
Page 259: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 265: ...9 DIMENSIONS 9 6 MEMO ...
Page 273: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 339: ...12 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 12 34 MEMO ...