80
System control (for Mr.Slim)
System Name
System Diagram
Features
Parts Required in Addition
to Standard SystemCom-
ponents (Indoor / Outdoor
Units, Remote Controller)
G. Timer operation
* For control by external timer,
refer to Remote/ local com-
bined control operation".
—
• Weekly timer:
In addition to ON/OFF, up to 8 tempera-
ture patterns can be set for each day of
the week.
* Only one timer can be selected; the auto
off, simple and weekly timers cannot be
combined.
• Simple timer:
Start and stop operations can each be
performed once within 72 hours (can be
set in 1-hour increments).
• Auto off timer:
Operation is stopped when the pre-
set time elapses following the start of
operation. The time can be set from 30
minutes to hours in 30-minute incre-
ments.
* Only one timer can be selected; the simple
and auto off timers cannot be combined.
MA Remote controller
(PAR-30MAA)
H. Interlock operation
with peripheral
equipment
• Connecting a Lossnay ventilator and an
indoor unit enables control of interlock/
solo ventilation operation and airflow.
(Only the microcomputer type Lossnay
ventilator can be used.)
I. Central control
• Connecting the M-NET connection
adapter to outdoor unit enables connec-
tion of MELANS system controller (for
M-NET).
• When using A-control operation, the
number of indoor units in a MELANS
system is limited to the number of
outdoor units. (Simultaneous twin, triple
and quad units are counted as 1 unit.)
• Number of controlled outdoor units
Central controller: 50 units
Group remote controller (PAC-SC-
30GR): 16 units
M-NET adapter
(Option PARTS)
Central controller
(G-50A)
Group remote controller
(PAC-SC30GR), etc.
J. Demand control
• Demand control is available by external
input. In this mode, power consumption
is decreased within the range of usual
0-100%.
Adapter to input external
demand signals.
(PAC-SC36NA)
Relay box
(Part to be provided at
your site )
Remote operating panel
(Part to be provided at
your site)
K. Rotation
• Rotation
Main and sub unit operate alternately
according to the interval of roration set-
ting.
• Back-up
When abnormality occurs while op-
eration, it changes into operating the
backup unit, and operation is continued.
• 2nd stage cut-in
· Number of operating units is deter-
mined according to the room tempera-
ture and set point.
· When room temperature becomes
higher than set point, standby unit
starts.(2 units operation)
· When room temperature falls below set
point -°C, standby unit stops.
(1 unit operation)
This function is availa-
ble when only 2 indoor
units are connected
to each PUHZ type
outdoor unit.
Application model
Indoor unit
PLA-RP · BA2 / BA#2.UK
PCA-RP · KAQ / HAQ
PKA-RP · HAL / KAL
PSA-RP · GA#1
PEAD-RP · JA(L)Q / GAQ
Indoor unit
Remote
Controller
Lossnay
ventilator
Indoor unit
Outdoor unit
Adaptor to input
external demand
signal
Relay box
Remote
Operating panel
Power
supply
unit
Outdoor
unit
Indoor
unit
Remote
Controller
Central controller, etc.
<Connection with M-NET system>
Enables control of start
and stop.
Enables control of Mitsubi-
shi Lossnay ventilator by
remote controller.