87
System control (for Mr.Slim)
No controll
No controll
No controll
The ability to save : 80%
The ability to save : 70%
The ability to save : 75%
The ability to save : 70%
Damand : 75%
Setting the remote controller
External input
Operation of the outdoor unit
SW2
SW3
Orange
1
3
Brown
Red
CNDM
Y
X
X
Y
A
Circuit diagram example
(Demand function)
C
External input adapter
(PAC-SC36NA)
B
On-site arrangement
D
Outdoor unit control board
X: Relay
E
Max. 10 m
(DC15V, 0.1Aor more)
F
Power supply for relay
6.2 On demand control (Local wiring)
By performing the following modifi cation, energy consumption can be reduced to 0–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the contact input of an ON / OFF switch is added
to
the CNDM connector (option) on the control board of the outdoor unit.
Complete the circuit as shown when using the external input adapter (PAC-SC36NA). (Option)
By setting SW7-1 on the control board of the outdoor unit, the energy consumption (compared to the normal consumption)
can be limited as shown below.
SW7-1
SW2
SW3
Energy consumption
Demand
function
ON
OFF
OFF
100%
ON
OFF
75%
ON
ON
50%
OFF
ON
0%(Stop)
■
Operation when using both remote controller settings and external input
When using both the remote controller and external input, the lower setting value will be valid.