5
2. Installation location
• Leave open in two directions.
• If the wall height (H) exceeds the overall height of the unit, add the dimension
shown as “h” to the dimension shown as “*”. (h: Wall height (H) - overall unit height)
• When there is a wall in front of the units, limit the maximum number of units con-
nected together to 4 and allow 1,000 mm of space or more between every 4 units to
provide space for airflow and space for people to pass through.
3. Transporting the unit
Fig. 2-8
Use care in the following areas when handling the units.
When using a forklift or similar equipment to load or unload the units, always insert
the forks of the forklift into the square-shaped openings provided (as shown in the
illustration on the left) and transport. It is dangerous to insert the forks from the side
as the unit has a center of gravity that is not at the center of the unit. It may tilt away
from its center of gravity and become unstable.
3.1. Transporting by forklift (Fig. 3-1)
• When transporting the unit by forklift, always insert the forks into the square-shaped
openings at the base of the unit.
Note:
1. Always use care when transporting a unit by forklift on rainy days as slip-
page can occur.
2. Never use dangerous sudden movements, such as accelerating or applying
the brakes suddenly or turning the steering wheel quickly, when transporting
the unit by forklift.
3.2. Transporting by pallet truck (Fig. 3-2)
• When using a pallet truck to transport the unit, insert the forks from the side of the
unit.
Note:
The center of gravity of the unit is not at the dimensional center of the unit.
Therefore, make sure that the forks of the pallet truck pass completely under
the unit and extend out the opposite side before lifting the unit for transport.
Fig. 3-1
Fig. 3-2
3
2
1
1
2
2
3
2
2
2
2
3
1
4
2
2
2
1
Wall height (H)
2
Front side
3
Leave open
4
No wall height restriction
1
Square-shaped opening
for inserting the forks.
2
Forklift
3
Forklift forks
4
Protective cover
5
Wood slats (Provide these
for the unit to rest against
when the forks are tilted
back for transport.)
4
5
3
2
1
1
2
3
1
Space for inserting the
forks of a pallet truck.
2
Pallet truck
3
Insert
(mm)
Min.
450*
Min.
450
Min.
450
Min.
450
Min.
450
Min.
250*
Min.
90
Min.
90
Min.
90
Min.
90
Min.
90
Min.
90
Min.
90
Min.
90
Min.
90
Min.
90
Min.
1000
Min.
1000
Min. 250*
Min.
900
Min. 45