Mitsubishi Netcom User Manual
Rev 3 02/24/2009
35
upsSecondsOnBattery OBJECT-TYPE
SYNTAX
NonNegativeInteger
-- UNITS seconds
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"If the unit is on battery power, the elapsed time in
seconds
since the UPS last switched to battery power, or the time
since
the network management system was last restarted, whichever
is less.
Zero shall be returned if the unit is not on battery
power."
::= { upsBattery 2 }
upsEstimatedMinutesRemaining OBJECT-TYPE
SYNTAX
PositiveInteger
-- UNITS minutes
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"An estimate of the time in minutes until the battery is
depleted
under the present load conditions if the utility power is
off and
remains off, or if it were to be lost and remain off."
::= { upsBattery 3 }
upsEstimatedChargeRemaining OBJECT-TYPE
SYNTAX
INTEGER
-- UNITS percent
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"An estimate of the battery charge remaining expressed as a
percent of full charge."
::= { upsBattery 4 }
upsBatteryVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
-- UNITS 0.1 Volt DC
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The magnitude of the present battery voltage (0.1 Volt
DC)."
::= { upsBattery 5 }
upsBatteryCurrent OBJECT-TYPE
SYNTAX
INTEGER (-2147483648..2147483647)
-- UNITS 0.1 Amp DC
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The present battery current (0.1 Amp DC)."
::= { upsBattery 6 }
upsBatteryTemperature OBJECT-TYPE
SYNTAX
INTEGER (-2147483648..2147483647)
-- UNITS degrees
Centigrade
ACCESS
read-only