10
4. Alarm Contact Output (Optional)
Note that alarm contact output will not operate unless control power is applied to the MDU and the alarm contact output.
●
●
The MDU is used as separate installation.
●
Alarm contact output is a factory installed option. It cannot be installed after.
Caution
4.1 Contact capacity and combinations for alarm contact output
●
Refer to the table below for alarm contact output contact capacity.
COS
φ
= 1
COS
φ
= 0.4,
L/R = 0.007
125 VAC
3 A
2 A
250 VAC
3 A
2 A
30 VDC
2 A
2 A
100 VDC
0.4 A
0.3 A
Accessory
device name
PAL
OAL
Part names
PAL
○
-
Control power
P2
P1
LED display
PAL
618 PALc
Contact output
617 PALa
TI
○
○
Control power
P2
P1
LED display
OAL
PAL
618 PALc
Contact output
617 PALa
518 OALc
517 OALa
Alarm
name
4.2 Precautions for alarm contact output usage
●
Control power is required for alarm contact output. Connect control power to terminals L1 and L2. (No polarity.)
Rated voltage: 100 to 240 VAC/DC common 50/60 Hz
VA consumption: 5 VA
Use a power supply to prevent power outages when the MDU Breaker is tripped.
●
Note that alarm contact output will not operate unless control power is applied to the MDU. Confirm that the MDU Breaker and the MDU are
securely connected with a connection cable.
●
Make sure that terminal connections are tightened at the optimal tightening torque (0.9 to 1.2 N
・
m).
●
Alarm contact output may generate a slight noise when control voltage is applied. This is due to the operation of the internal electronic circuit,
and is not an abnormality.
●
If alarm contact output is attached, internal accessory devices cannot be installed on the right pole side.
Caution