[Wiring for products with CC-Link communication]
●
CC-Link communication terminals DA, DB, DG, and SLD are included with CC-Link communication MDUs.
Connect these to the CC-Link transmission line. Never connect non-transmission line terminals (such as the L1 and L2 control power supply terminals).
The CC-Link transmission line forms a small-signal circuit. Connecting it improperly is extremely dangerous.
●
The CC-Link transmission line forms a small-signal circuit. Install it at least 10 cm away from strong circuits.
Allocate a distance of 30 cm or more in the case of connection in parallel for a long distance.
Caution
Danger
[Wiring for products with electric energy pulse output]
●
The 114 and 113 terminals for pulse output use are available on the MDU that has the electric energy pulse output function.
●
The pulse output line forms a small-signal circuit. Install it at least 10 cm away from strong circuits. The wiring length is determined by various
conditions such as the anti-noise performance of the pulse receiver. However, the wiring should not exceed 100 m.
●
If using A/C for the pulse output power supply, make sure that the pulse receiver does not erroneously operate due to leak current caused by
conduit capacitance.
Caution
Caution
The products listed in page 13 may not be compatible with some electric wires. For details, contact the pin terminal (crimp terminal) manufacturer directly.
However, if using a pin terminal (crimp terminal) with a metallic portion longer than 7 mm, cut the metallic portion to 7 mm as shown in the figure below.
●
After wire connection, attach the removable connector and tighten the screws. The adequate tightening torque is 0.2 to 0.3 N
・
m.
Tighten the (two) screws.
(Tightening torque: 0.2 to 0.3 N
・
m)
Pin terminal
Metallic portion
7 mm
Cut here.