6.3.2 Measurement rated values/measurement range and accuracy
Electric current total present value
I3
(I1 + I3) / 2
(I1 + I2 + I3) / 3
Maximum phase applicable phase
I3
I1, I3
I1, I2, I3
I1, I2, I3, IN
Line system
Single-phase 2-wire
Single-phase 3-wire
Three-phase 3-wire
Three-phase 4-wire
Rated current In (A)
Accuracy (
±
1.0% of In) (*)
Measurement lower limit current (1% of In)
Measurement upper limit current (In
×
2)
400
±
4.0 A
4.0 A
800 A
630
±
6.3 A
6.3 A
1260 A
800
±
8.0 A
8.0 A
1600 A
Setting value
0 to 15 min. (per 1 min.)
Item
Demand time limit
Display
Blinks at measurement upper limit current
Fixed at measurement upper limit current
Communication
0 A
Less than 1% of In
Measurement upper limit current exceeded
(1) Electric current
[1] The present value is the effective value during a single cycle.
[2]
“
Each-phase
”
means the 1-, 2-, 3-, and N-phase.
[3] Totals (average value) are calculated as follows when setting the phase and wire (factory setting is three-phase three-wire for three-pole
products, and three-phase four-wire for four-pole products).
The present value of the maximum phase electric current and present value of the maximum phase electric current demand indicate the maximum
value of the following phases via setting the phase and wire.
[4] The electric current demand time limit can be set as follows. The demand time limit is a bulk setting value that includes other measurement
elements. (Factory setting is two min.)
[5] The all-phase demand maximum value indicates the maximum value of the demand value for all phases, from when usage began (after
previous reset) to now.
[6] The electric current measurement rated value, measurement range, and measurement accuracy are shown below.
[7] Display/communication values will be as follows in the following conditions.
* The measurement accuracy is the ratio versus In, regardless of the rated voltage.
Current setting Ir (A)
200-400 adjustable
300-630 adjustable
400-800 adjustable
Summary of Contents for NF400-HEW