23
Monitoring starts when the load current for any phase reaches or exceeds 10% of the measurement rated current.
The alarm is output to display/over communication when an energization phase equal to or less than the maximum
phase current
×
10% is generated when monitoring starts and after 30 seconds have passed.
Set via communication or on the display
Function: ON/OFF
(Factory setting is OFF.)
Pick up current: 10% fixed (no settings)
Operating time: 30 s fixed (no settings)
Set to either self-hold or automatic reset via communication or on the display.
Reset the alarm via communication or on the display.
Reset method
Self-hold
Automatic reset
Automatically resets when the cause of the alarm is removed.
Alarm details
Setting method
Reset method
(4) ILA_AL (electric current open phase alarm)
Monitoring starts when the load current for any phase reaches or exceeds 10% of the measurement rated current.
The alarm is output to display/over communication when an energization phase equal to or less than the maximum
phase current
×
30% is generated when monitoring starts and after 30 seconds have passed.
Set via communication or on the display
Function: ON/OFF
(Factory setting is OFF.)
Pick up current: 30% fixed (no settings)
Operating time: 30 s fixed (no settings)
Set to either self-hold or automatic reset via communication or on the display.
Reset the alarm via communication or on the display.
Reset method
Self-hold
Automatic reset
Automatically resets when the cause of the alarm is removed.
Alarm details
Setting method
Reset method
(5) IUB_AL (electric current unbalance alarm)
Monitoring starts
Maximum
phase current
Measurement rated
current
×
10%
Electric current open phase
alarm generated
30 s elapsed
Maximum phase current
×
10%
I1
I2
I3
Time
Measurement
value
Monitoring starts
Maximum
phase current
Measurement rated
current
×
10%
Electric current unbalance
alarm generated
30 s elapsed
Maximum phase current
×
30%
I1
I2
I3
Time
Measurement
value