- 100 -
Checking code
1302
Meaning, detecting method
Cause
Checking method & Countermeasure
High pressure
abnoramlity 2
(Outdoor unit)
When pressure sensor detects
0.098MPa or less just before
starting of operation, error stop
is observed with code No.“1302”
displayed.
(1) Fall in internal pressure
caused by gas leak.
(2) Pressure sensor trouble.
(3) Film breakage.
(4) Coming off of pin in connector
portion, poor contact.
(5) Broken wire.
(6) Pressure sensor input circuit
trouble on control circuit
board.
See
Trouble check of pressure
sensor.
1500 Overcharged
refrigerant
abnormality
1. If the discharge SH 10K is
detected during operation (at
first detection), the outdoor
unit stops at once. The 3
minutes restart prevention
mode is entered. After three
minutes, the outdoor unit
starts up again.
2. If the discharge SH 10K is
detected again within 30
minutes after the outdoor unit
stops (second detection), an
abnormal stop is applied, and
“1500” is displayed.
3. If discharge SH 10K is
detected more than 30
minutes after the outdoor unit
stops, the state is the same
as the first detection and the
same operation as 1. above
takes place.
4. The abnormal stop delay
period is in effect for 30
minutes after the outdoor unit
stops. The abnormal stop
delay period LED turns ON
during this time.
(1) Excessive refrigerant
charge.
(2) Main circuit board thermistor
input circuit trouble.
(3) Thermistor mounting trouble
(TH11, TH12).
Refer to the section on judging
the refrigerant volume.
Check the sensor detection
temperature and pressure with
the LED monitor.
2500 Leakage
(water)
abnormality
When drain sensor detects
flooding during drain pump OFF.
(1) Water leak due to humidifier
or the like in trouble.
Check water leaking of humidifier
and clogging of drain pan.