- 118 -
Checking code
Meaning, detecting method
Factor
Checking method & Remedy
6831
6834
6832
6833
(1) The remote control line of
the MA remote controller or
the indoor unit has a poor
contact.
(2) All remote controllers are
slaves.
(3) The wiring specifications are
not observed.
1. Wire length
2. Wire thickness
3. Number of remote
controllers
4. Number of indoor units
(4) After the remote controller is
connected, disconnection of
the remote controller without
resetting the power.
(5) Noise enters the transfer
path of the remote controller.
(6) The transmission/reception
circuit of the remote
controller of the indoor unit is
poor.
(7) The transmission/reception
circuit of the remote
controller is defective.
(1) The remote control line of
the MA remote controller or
the indoor unit is in poor
contact.
(2) It is set on two or more main
remote controllers.
(3) The indoor unit address is
set twice.
(4) Noise enters the remote
controller line.
(5) The wiring specifications are
not observed.
1. Wire length
2. Wire thickness
3. Number of remote
controllers
4. Number of indoor units
(6) The transmission/reception
circuit of the remote
controller is defective.
(1) Check the transmission lines
of the indoor unit and MA
remote controller for
disconnection and looseness.
(2) Check the power supply to
the main power and remote
controller lines.
(3) Check whether the tolerable
range of the MA remote
controller line is exceeded or
not.
(4) Check the main/slave setting
of the MA remote controller.
(5) Diagnose the remote
controller.
(Remote controller IM
description)
Result:
[OK]: No problem in the remote
controller
(wiring specifications
check)
[NO]: Replace the remote
controller
[6832, 6833, ERC]:
Noise is the cause.
< To (6) >
(6) Check the transmission
waveform and noise on the
transmission signal of MA
remote controller line.
(7) If no problem is present in
items.
(1) to (6) above, replace the
indoor controller board or
MA remote controller.
The following states can be
checked from LED1 and
LED2 on the indoor
controller board.
• LED1 is lit at the same time.
The main power is
supplied to the indoor unit.
• LED2 alone is lit.
Power is supplied to the
MA remote controller line.
1. Communication between the
MA remote controller and the
indoor unit is not done
properly.
2. No proper data has been
received for 3 minutes.
1. Communication between the
MA remote controller and the
indoor unit is not done
properly.
2. No proper data has been
received for 2 minutes.
1. Communication between the
MA remote controller and the
indoor unit is not done
properly.
2. When transmission is
impossible because the
emptiness of the transfer path
cannot be checked.
Indoor unit
: 3 minutes
Remote controller : 6 seconds
1. Communication between the
MA remote controller and the
indoor unit is not done
properly.
2. When the transmitted data is
received at the same time and
compared, the different state
continues 30 times.
MA
Communication
no reception
error
MA
Communication
start bit error
MA
Communication
synchroniza-
tion recovery
error
MA
Communication
transmission
/reception
hardware error