1
2
MA remote controller
TB15
Logical 1
Logical 0
Logical 1
Logical 1
Indoor unit
The MA remote control and indoor unit communicate with the current tone burst method.
(1) Symptoms caused by infiltration of noise on transmission cable
If noise, etc., infiltrates the transmission cable and the communication between the MA remote control and indoor
unit is cut off for three consecutive minutes, a MA communication error (6831) will occur.
(2) Confirmation of transmission specifications and waveform
(1) 2msec/bit
±
5% must be satisfied
(2) Voltage across terminal No.1-2 must
be within range shown on left.
A1, B2: No polarity
Across terminal No. 1-2 :
Power supply (8.5V to 12VDC)
Transmission waveform (Across terminal No. 1-2)
- 133 -
2. MA remote control transmission