- 53 -
˚C
˚C
˚C
LIMIT TEMP.
˚C
LIMIT TEMP.
[Time selection (
) ((
))] button
[Time selection (
) ((
))] button
[PROCEDURE]
1. Set the air conditioner to the off state with the remote controller [ON/OFF] button. The remote controller display shifts to the OFF window display
shown at the left.
2. When the [CHECK] and [Mode selection] buttons
1
are pressed and held down at the same time for two seconds, the remote controller switches to
the remote controller function selection mode and the “OPERATION MODE DISPLAY SELECTION MODE” window appears. The other three modes
can be selected by operating the [TEMP.] (
) button
2
3
or (
) button
. Display the mode whose function you want to change.
OPERATION MODE DISPLAY SELECTION MODE (When you want to change the AUTO mode display)
• “AUTO” “COOL/HEAT” flashes and “ON” or “OFF” lights. Each time the [Time selection (
) or (
)] button
4
is pressed in this state, the “ON” and
“OFF” display is switched.
• When “ON” was selected, “AUTO” “COOL” or “AUTO” “HEAT” is displayed during AUTO mode operation.
• When “OFF” was selected, only “AUTO” is displayed during AUTO mode operation.
[When set temperature adjustment range in cool/dry mode is 19
°
C to 30
°
C]
2) Each time the [Time selection (
) or (
)] button
4
is pressed, the lower limit temperature value is increased or decreased. Set it to the desired
set temperature adjustment range.
ROOM TEMPERATURE DISPLAY SELECTION MODE (When you want to change room temperature display/no display)
• “88
°
C” flashes at the room temperature display and “ON” or “OFF” lights. Each time the [Time selection (
) or (
)] button
4
is pressed in this
state, the “ON” and “OFF” display is switched.
• When “ON” was selected, the room temperature is continuously displayed in the ON window.
• When “OFF” was selected, the room temperature is not displayed in the ON window.
SET TEMPERATURE RANGE LIMIT MODE (When you want to change the set temperature adjustment range)
1) Cool/dry mode temperature selection
“COOL/DRY” and “LIMIT TEMP.” light on the display and the set temperature adjustment range in the cool (dry) mode is displayed.
The lower limit temperature of the set temperature display flashes. This temperature value can be set and changed.
[Lower limit temperature adjustment range]: 19
°
C
30
°
C (Upper limit temperature 30
°
C is fixed. Only the lower limit temperature
can be changed.)
[When set temperature adjustment range was set to 24
°
C to 30
°
C]
3) When the [TEMP. (
)] button
2
is pressed after the setting above, the remote controller switches to the heat mode temperature selection window.
“HEAT” and “LIMIT TEMP.” light on the display and the heat mode set temperature adjustment range is displayed.
The upper limit temperature value can be changed by pressing the [Time selection (
) or (
)] button
4
, the same as cool/dry mode temperature
selection.
Upper limit temperature adjustment range: 17
°
C to 28
°
C (The lower limit temperature 17
°
C is fixed. Only the upper limit temperature can be
changed.)
3. At the end of selection of each function, release the remote controller function selection mode and display the OFF window by pressing the [CHECK]
and [Mode selection] buttons
1
at the same time for two seconds.
Perform this operation when you want to register the LOSSNAY, confirm the registered units, or delete the
registered units controlled by the remote controller.
The following uses indoor unit address 05 and LOSSNAY address 30 as an example to describe the
setting procedure.
[Setting Procedure]
1
Stop the air conditioner using the remote controller
A
[ON/OFF] button.
If the OFF display shown below does not appear at this time, step
2
cannot be performed.
2
Press and hold down the
[FILTER] and
c
B
[Louver] buttons at the same time for two
seconds. The display shown below appears. The remote controller confirms the registered
LOSSNAY addresses of the currently connected indoor units.
Make this setting only when interlocked operation with LOSSNAY is necessary with CITY MULTI
models.)
(This setting cannot be made with Mr. SLIM air conditioners.)
FUNCTION
TIMER SET
PAR-20MAA
D
G
E
H
ON/OFF
FILTER
CHECK TEST
TEMP.
FUNCTION
C
F
A
B
[3] Interlocking Setting that is Made on the MA Remote Controller
Lossnay interlocking setting