Before powering
Before powering
Before powering
Before powering
Removing the cover shows switches at the lower part of the remote controller unit. By operating these switches, the
controller main/sub, and other function will be set.
In normal case, do not change the setting except No.1 switch used to set the main/sub. (All setting at factory shipment
are "ON."
Set the address of the remote controller with the rotary switch.
Remote controller unit
Switch
Function
ON
OFF
Action by switching
Switch set timing
1
Remote controller
Main
Sub
main/sub
2
At powering of
Normal
Timer mode
remote controller
start up
start up
3
Cooling/heating display
Yes
No
Yes
No
at automatic setting
4
Inlet temperature
display
Sets one to "Sub" when connecting 2 sets in
1 group.
Sets to "Timer mode start up" so desired at power
failure return when the schedule timer is connected.
Sets to "No" when not desiring to display
"Cooling" or "Heating."
Sets to "No" when not desiring to display
inlet temperature.
Address setting range
Setting method
Main remote controller
101 ~ 150
Set to the lowest indoor main unit address + 100.
Sub remote controller
151 ~ 200
Set to the lowest indoor main unit address + 150.
Setting of rotary switch
Address No.
01 ~ 99
101 ~ 199 being added with 100
00
200
Note : To set addresses, use a precision screwdriver [(–), 20mm (w)], and apply load less than 19.6N.
Operating with a method other than above may damage the rotary switch.
❉
The address No. that can be set with ME remote controller is limited to 101 ~ 200.
The position of 100 will automatically be fixed to [1] when setting to "01 ~ 99", while it will automatically be fixed to [2] when setting to
"00."
❉
At factory shipment, the rotary switch was set to 01.
10 digits 1 digit
(left)
(right)
Selector switch
Remote controller unit
Remote controller unit
Rotary switch
Example: In case of address 108
remote
3. Remote controller
(1) MA remote controller (PAR-20MAA)
(2) ME remote controller (PAR-F27MEA)