Flow chart of initial operation mode
Start of initial operation mode
Step 1
P200
P250~P400
P450~P650
• Operation of only No.1 compressor
Exception : completed if discharge super heat reaches above 25˚C within
5 minutes of start up.
:
:
:
Step 3
• Forced operation of only No.2 compressor
• Completed in the integrated operation time of 5 minutes
Completion of initial operation
f 50Hz and completed in the continuous integrated operation time
of 20 minutes or the integrated time of 90 minutes.
f 60Hz and completed in the continuous integrated operation time
of 20 minutes or the integrated time of 90 minutes.
For the first 30minutes f 60Hz, 30minutes and on f 85Hz.
No.2 compressor not in operation.
Completed in the integrated operation time of 40 minutes.
P450~P650 types
P200~P400 type
- 73 -
Operation
mode
Heat exchanger
capacity
Inverter
control
Number
of fans
Remarks
21S4b ON, 21S4c OFF
SV5b ON, SV5c OFF
10~100%
1
50%
21S4b, 21S4c ON
SV5b, SV5c
ON
5~100%
1
25%
21S4b, 21S4c OFF
SV5b, SV5c
OFF
15~100%
2
100%
Cooling
21S4b, 21S4c ON
SV5b, SV5c
OFF
10~100%
2
100%
Heating
21S4b, 21S4c OFF
SV5b, SV5c
OFF
0%
0
100%
Defrost
Operation
mode
Note 1 : 21S4b and 21S4c are not energized during cooling cycle and energized during heating cycle.
Note 2 : SV5b and SV5c are not energized when it is open and energized when it is closed.
Note 3 : While the unit is stopped, 21S4b and 21S4c are not energized and in cooling cycle, and SV5b and SV5c are opened.
Heat exchanger
capacity
Inverter
control
Remarks
21S4b ON
SV5b
ON
5~100%
50%
21S4b OFF
SV5b
OFF
10~100%
100%
Cooling
21S4b ON
SV5b
OFF
10~100%
100%
Heating
21S4b OFF
SV5b
OFF
0%
100%
Defrost
[P400-P650types]
[P200-P350types]
8. Subcool coil control (Linear expansion valve <LEV1>)
• The amount of super heat is controlled and kept constant based on the bypass outlet temperature (TH8) of
subcool coil every 30 seconds.
• The degree of opening is controlled based on the subcool coil outlet/inlet temperature (TH5, TH7), high pres-
sure (Pd), and discharge temperature.
However, the LEV will be closed (0) during heating operation and when the compressor is stopped, and it will
be open during cooling operation with thermo off.
• It stays open at 480 during defrost operation.
9. Control at initial startup
• If the unit is started within 2 hours of power on when the outdoor temperature is below a certain degree
(below 5˚C for cooling operation and below -5˚C for heating operation), the unit will be on the stand-by mode
and will not start for 30 minutes after power on. (P200 type only)
• When the unit is started for the first time, it will run the following course of operation.
(3) Patterns of outdoor unit heat exchanger capacity control