7-1-1. Setting the number of the minimum management group
Sets the number of the minimum management group using the system remote controller.
(The minimum management group = 1 is set when shipped.)
Groups managed with the system remote controller.
Groups between the minimum management group number and the minimum management group + 31.
Examples:Groups 1 - 32 are managed when the minimum management group = 1.
Groups 12 - 43 are managed when the minimum management group = 12.
The minimum management group number set with this function appears as a group number in the block at
the top-left of the display.
Example: When the minimum management group = 12
ON
COLLECTIVE
GROUP
OFF
CENTRALIZED
AUTO
BY-PASS
HEAT EX.
CHECK
FILTER
PROHIBIT
MODE LOCK
FILTER
SKIP
TEMP.
MODE
ON/OFF
˚C
ON/OFF
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Group number of each block
Changing the Minimum Management Group Number
(1)
Press the
PROHIBIT
switch twice in the initial setting mode.
The block at the top-left is selected and the current minimum management group number is displayed.
(2)
The minimum management group number is incremented each time the
switch is pressed, and
decremented each time the TEMP.
switch is pressed.
NOTE: • The minimum management group number may be set between 1 and 50.
• When the minimum management group number is set to 20 or higher the group number for the
block for the corresponding group will exceed 50. In this case indoor units cannot be registered
in the block for which the group number is 51 or higher.
(3)
After selecting the minimum management group number in (2) above, press the
PROHIBIT
switch twice to
register the new minimum management group number.
NOTE: The minimum management group number setting is necessary when the system remote controller
is set up as either a master or slave. (This is not necessary if the minimum management group
number remains at the default value of 1 set before shipment.)
Group number : 12