7-3. Emergency stop mode setting
The following settings are required when emergency stop input is received at the external input pin of the
system remote controller.
[Setting]
(1)
Following system start-up communication, press the
COL./GROUP
and
ON/OFF
switches simultaneously for
more than two seconds in the group operation screen or collective operation screen to display the
following and enter the emergency stop mode.
ON
COLLECTIVE
GROUP
OFF
CENTRALIZED
AUTO
BY-PASS
HEAT EX.
CHECK
FILTER
PROHIBIT
MODE LOCK
FILTER
SKIP
TEMP.
MODE
ON/OFF
˚C
ON/OFF
(2)
When the
COL./GROUP
and
ON/OFF
switches are again pressed simultaneously for more than two seconds, the
following is displayed, the emergency stop input mode is cleared, and the external timer mode is
selected.
ON
COLLECTIVE
GROUP
OFF
CENTRALIZED
AUTO
BY-PASS
HEAT EX.
CHECK
PROHIBIT
MODE LOCK
FILTER
SKIP
TEMP.
ON/OFF
˚C
ON/OFF
FILTER
MODE
NOTE: See the installation manual for the system remote controller for details of connecting the emer-
gency stop input cable.
8. Specifications
Specifications for this equipment
In addition to [
CENTRALIZED
] and
OFF
, [
] blinks
for two seconds in the group number display. Emergency
stop input is then possible.
In addition to [
CENTRALIZED
] and
OFF
, [
] blinks
for two seconds in the group number display. The emer-
gency stop input mode is then cleared and the external pro-
gram timer may be connected.
Item
Power supply
Electricity consumption
Environmental conditions for
usage
Weight
External dimensions
(H
×
W
×
D)
Details
DC30 V (power supplied from the outdoor unit or a power unit for
transmission lines (model: PAC-SC34KUA))
1 W
Temperature 0 to 40
°
C, humidity 30 to 90 % RH
(with no condensation)
0.2 kg
120
×
130
×
18 (mm)