4. Zone Control Interface
4.1. Installation
4.1.1 Choosing the zone controller installation location
• Do not install the zone controller in outdoor location as it is designed for indoor installation only. (The zone controller circuit board and casing are not waterproof.)
• Avoid locations where the zone contoroller is exposed to direct sunlight or other sources of heat.
• Select a location where easy wiring access to the power source is available.
• Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
• Select a level location that can bear the weight and prevent vibration of the zone contoroller.
• Avoid locations where the zone contoroller is exposed to oil, steam, or sulfuric gas.
• Do not install in location that ambient temperature exceeds 60°C and relative humidity exceeds 80%.
• Do not install zone control interface on top of the indoor unit.
4.1.2 Installing the zone controller
(Fig. 4.1.1, 4.1.2, 4.1.3, 4.1.4)
1. Remove 2 screws (
A
Screw) from zone controller and remove the cover. (See
Fig. 4.1.1)
2. Install the 4 screws (locally supplied) in the 4 holes (
C
Hole).
Note: To prevent the unit from falling off the installation location, select the
appropriate screws(locally supplied) and secure the base horizontally
to the appropriate installation location. (See Fig. 4.1.2)
A
Screw
B
Cover
C
Hole for installation
Weight
PAC-ZC40/80L-E: 2.5kg PAC-ZC40/80H-E: 2.7kg
Allowable ambient temperature
0 to 60°C
Allowable ambient humidity
80% RH or less
B
A
<Fig. 4.1.1>
<Fig. 4.1.2>
Service space
Wall
Floor
30mm or
more
30mm or more
Cover
Cover
Base
Base
<Fig. 4.1.3>
Service space
<Fig. 4.1.4>
Service space
Top
Bottom
Pull the cover to the
front and remove it.
Slide the control box cover
until the bottom of the cover
comes into contact with the
bottom of the control box.
Remove the 2 screws
A
(control box cover screws).
Cover
Base
1
2
3
Top
Bottom
Top
Bottom
Front
Unit:mm
3-ELECTRIC WIRE INLET
When installed on a wall: Lower side
69
C
C
C
C
278
(11.5)
11.5
336
10
22
313
200
{
12
{
5