 Connecting the receiver board connector to the control circuit board

 Removing the beam and the electrical box cover

• Remove the beam.
• Loosen the two screws at the bottom of the electrical box cover,
  and then slide the cover to the left to remove it.
• Pull down the electrical box.

{

Electrical box fixing screw 

   Electrical box cover fixing screw

Electrical box cover

Beam

• Pass the cord through the bush at the top right of the electrical box.
• Connect the connector to CN90 on the right of the control board.
• If  the cord is loose, bundle it using the clamps under the above bush.

CN90

Bush

Calmps

Calmps

 Remote control holder

• To install the wireless remote controller on a wall, first attach the remote control holder to a wall.

Fitting remote control into holder

 Fix the remote control holder to the wall using 

    the 2 wood screws provided.

 Insert the remote control into the holder.

 Push the remote control against the wall.

Removing remote control

Ɣ

 Pull the top of remote control forward.

NOTE : The remote signal will reach the receiver over a distance of approx. 7m in a straight line and approx. 45°
             left or right. If the infrared receiver is affected by fluorescent light (especially, inverter type), it may not be
             able to receive the signal. Take this into consideration when installing fluorescent lights or replacing them. 

Also on the 
opposite side

 Reinstalling the removed components

• Reinstall the removed components in reverse order. (The brand lavel case is not needed.)

* The positions of the connectors may be different according to the model.
  Please refer to the wiring diagram to confirm the positions of the connectors.

 Laying out the lead wire

• Pass the lead wire for receiver through the retaining clips.
• Fix the lead wire for receiver with the clips on the ceiling side
  of the unit.

Retaining clip

Clips on the ceiling side 

Wireless Remote Controller Kit

for Ceiling Suspended models

PAR-SL94B-E

Summary of Contents for PAR-SL94B-E

Page 1: ...systems per group One or more wireless light receivers must be installed for each refrigerant system Number of units controlled Adapter wiring 9 wire cord standard accessory with connector is connected to the connector CN90 on the indoor unit control board Light receiver range 7m or less at within 45 degrees to the front of receiver the range varies with conditions Operating conditions Temperature...

Page 2: ...the grille Remove the screw holding the side panel and then slide the side panel forward to remove it Side panel Slide forward Catach retaining the intake grille Remove the screw holding the side panel Removing the existing brand label case Remove the brand label case name plate with MITSUBISHI ELECTRIC from the bottom right of the unit If it is difficult to remove the case use a flat blade screwd...

Page 3: ...sert the remote control into the holder Push the remote control against the wall Removing remote control Ɣ Pull the top of remote control forward NOTE The remote signal will reach the receiver over a distance of approx 7m in a straight line and approx 45 left or right If the infrared receiver is affected by fluorescent light especially inverter type it may not be able to receive the signal Take th...

Page 4: ...O STOP AUTO START h min RESET SET CLOCK MODEL SELECT The positions of the connectors may be different according to the model Please refer to the wiring diagram to confirm the positions of the connectors Test Run Measure an impedance between the power supply terminal block on the outdoor unit and the ground with a 500V Megger and check that it is equal to or greater than 1 0 M Turn on the main powe...

Page 5: ...d by the unit is entered 3 beeps 3 beeps of 0 4 seconds duration will be heard Reenter the mode number selecting If the signal was not received by the sensor or an error occurred during transmission you will not hear a beep or a double beep may be heard Press the button again Selecting the setting number Use the and buttons to change the LOSSNAY connectivity setting to 02 Direct the wireless remot...

Page 6: ...he function that can be set for the indoor unit Table 4 Itemized functions of the entire refrigerant system select unit number 00 Mode Settings Not available Available Approximately 4 minutes wait period after power is restored Indoor unit operating average Set by indoor unit s remote controller Remote controller s internal sensor Not supported Supported indoor unit is not equipped with outdoor ai...

Page 7: ...p Beep Beep Beep Off Approx 2 5 sec On 0 5 sec On 0 5 sec On 0 5 sec On 0 5 sec Off Approx 2 5 sec On 0 5 sec On 0 5 sec Repeated Number of blinks beeps in pattern indicates the check code in the following table i e n 5 for P5 Number of blinks beeps in pattern indicates the check code in the following table nth 1st 2nd 3rd 1st 2nd Self check starts Start signal received Beeper sounds Ɣ Refer to th...

Page 8: ...U7 U9 UH Others Other errors Refer to the technical manual for the outdoor unit For details check the LED display of the outdoor controller board Compressor overcurrent interruption On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code display in the LCD Wired remote controller Check code CITY ...

Reviews: