Pair Number Setting

• This is  the setting to specify the unit to operate with the wireless remote controller.
• Make setting for J41, J42 (Jumper wire) of indoor controller board and the pair number of wireless remote cotroller.
• The pair number setting is available with the 4 patterns as shown in the following table. Make setting for the pair number
  (J41, J42) of indoor controller board and the pair number of wireless remote controller which is used
  as shown in the following table. *The initial setting is Pair No. “0”.

 Press the SET button with something sharp at the end.

    Start this operation from the status of remote controller display turned off.

MODEL SELECT

 blinks and Model No. is lighted.

 Press the        button twice continuously. Pair No. “0” blinks.

 Press the temp            button to set the pair number you want to set.

 Press the SET button with something sharp at the end.

    Set pair number is lighted for 3 seconds then turned off.

 Pair No. of wireless remote controller Indoor PC board

Initial setting
  Cut J41
  Cut J42 
Cut J41, J42

0
1
2

  3 ~ 9

CN90

min

Jumper wire (J41, J42)

ON/OFF

TEMP

FAN

VANE

MODE

CHECK

LOUVER

TEST RUN

    AUTO STOP

     AUTO START

h

min

RESET

SET

CLOCK

MODEL SELECT

 

* The positions of the connectors may be 
  different according to the model.
  Please refer to the wiring diagram to 
  confirm the positions of the connectors.

Test Run

Measure an impedance between the power supply terminal block on the outdoor unit
and the ground with a 500V Megger and check that it is equal to or greater than 1.0 M

.

 Turn on the main power to the unit.

 Press the         button twice continuously.

         (Start this operation from the status of remote controller display turned off.)

TEST RUN

 and current operation mode are displayed.

 Press the         (               ) button to activate COOL    mode, then check whether

         cool air is blown out from the unit.

 Press the         (               ) button to activate HEAT    mode, then check whether

         warm air is blown out from the unit.

 Press the         button and check whether strong air is blown out from the unit.

 Press the         button and check whether the auto vane operates properly.

 Press the ON/OFF button to stop the test run.

TEST RUN

MODE

MODE

FAN

VANE

NOTE : • Point the remote controller towards the indoor unit receiver 
               while following steps 

 to 

.

             • It is not possible to run in FAN, DRY or AUTO mode. 

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

NOT AVAILABLE

SWING

TEST

RUN

 

3

4

Wireless Remote Controller Kit

for Ceiling Suspended models

PAR-SL94B-E

Summary of Contents for PAR-SL94B-E

Page 1: ...systems per group One or more wireless light receivers must be installed for each refrigerant system Number of units controlled Adapter wiring 9 wire cord standard accessory with connector is connected to the connector CN90 on the indoor unit control board Light receiver range 7m or less at within 45 degrees to the front of receiver the range varies with conditions Operating conditions Temperature...

Page 2: ...the grille Remove the screw holding the side panel and then slide the side panel forward to remove it Side panel Slide forward Catach retaining the intake grille Remove the screw holding the side panel Removing the existing brand label case Remove the brand label case name plate with MITSUBISHI ELECTRIC from the bottom right of the unit If it is difficult to remove the case use a flat blade screwd...

Page 3: ...sert the remote control into the holder Push the remote control against the wall Removing remote control Ɣ Pull the top of remote control forward NOTE The remote signal will reach the receiver over a distance of approx 7m in a straight line and approx 45 left or right If the infrared receiver is affected by fluorescent light especially inverter type it may not be able to receive the signal Take th...

Page 4: ...O STOP AUTO START h min RESET SET CLOCK MODEL SELECT The positions of the connectors may be different according to the model Please refer to the wiring diagram to confirm the positions of the connectors Test Run Measure an impedance between the power supply terminal block on the outdoor unit and the ground with a 500V Megger and check that it is equal to or greater than 1 0 M Turn on the main powe...

Page 5: ...d by the unit is entered 3 beeps 3 beeps of 0 4 seconds duration will be heard Reenter the mode number selecting If the signal was not received by the sensor or an error occurred during transmission you will not hear a beep or a double beep may be heard Press the button again Selecting the setting number Use the and buttons to change the LOSSNAY connectivity setting to 02 Direct the wireless remot...

Page 6: ...he function that can be set for the indoor unit Table 4 Itemized functions of the entire refrigerant system select unit number 00 Mode Settings Not available Available Approximately 4 minutes wait period after power is restored Indoor unit operating average Set by indoor unit s remote controller Remote controller s internal sensor Not supported Supported indoor unit is not equipped with outdoor ai...

Page 7: ...p Beep Beep Beep Off Approx 2 5 sec On 0 5 sec On 0 5 sec On 0 5 sec On 0 5 sec Off Approx 2 5 sec On 0 5 sec On 0 5 sec Repeated Number of blinks beeps in pattern indicates the check code in the following table i e n 5 for P5 Number of blinks beeps in pattern indicates the check code in the following table nth 1st 2nd 3rd 1st 2nd Self check starts Start signal received Beeper sounds Ɣ Refer to th...

Page 8: ...U7 U9 UH Others Other errors Refer to the technical manual for the outdoor unit For details check the LED display of the outdoor controller board Compressor overcurrent interruption On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code display in the LCD Wired remote controller Check code CITY ...

Reviews: