background image

OPTIONAL

PA
R

T

S

E-134

Other function selections
Now that you know how to change LOSSANY connectivity setting, there are several other settings that can be changed as well.
The following table lists the various settings that can be changed through the remote controller and the default settings.

Function

Settings

Not available
Available
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not supported
Supported (indoor unit is not equipped with outdoor-air intake)
Not supported (indoor unit is not equipped with outdoor-air intake)
Energy saving cycle automitically enabled
Energy saving cycle automitically disabled
100Hr
2500Hr
No filter sign indicator
Quiet
Standard
High ceiling
No vanes
Equipped with vanes (No.1 set)
Equipped with vanes (No.2 set)

*1
*1

ż

ż

ż

ż

ż

ż

PCA-RP·KA

Power failure automatic recovery

Indoor temperature detecting

LOSSNAY connectivity

Auto mode (only for PUHZ)

Filter sign

Fan speed

Up/down vane setting

*1  Power failure automatic recovery initial setting depends on the connecting outdoor unit.

 Things to remember when entering function selections:

The basic procedure for entering function selections is the same as described for switching between LOSSNAY connectivity.

 However, there are some differences at step 

 for selecting the unit number, step 

 for selecting the mode number

 and step 

 for selecting the setting number.

 The following Tables 4 and 5 list the various function settings, mode numbers and setting numbers.
 Table 4 details the function of the entire refrigerant system while Table 5 shows the function that can be set for
 the indoor unit. 

Table 4. Itemized functions of the entire refrigerant system (select unit number 00)

Mode

Settings

Not available
Available (Approximately 4-minutes wait-period after power
is restored.)
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not supported
Supported (indoor unit is not equipped with outdoor-air intake)
Not supported (indoor unit is not equipped with outdoor-air intake)

Energy saving cycle automitically enabled
Energy saving cycle automitically disabled

01

02

03

05

Mode no.

Power failure 
automatic recovery

Indoor temperature 
detecting

LOSSNAY 
connectivity

Auto mode 
(only for PUHZ)

Setting no. Check

Remarks

1

2

1
2
3
1
2
3
1
2

Approximately 4-minutes wait-
period after power is restored.

Table 3.

Table 5. Itemized functions of the indoor unit (select unit numbers 01 to 04 or 07)

Mode

Settings

100Hr
2500Hr
No filter sign indicator
Quiet
standard
High ceiling
No vanes
Equipped with vaneas (No.1 set)
Equipped with vaneas (No.2 set)

07

08

11

Mode no.

Filter sign

Fan speed

Up/down vane 
setting

Setting no. Check

Remarks

1
2
3
1
2
3
1
2
3

Setting the unit numbers
Set “00” as the unit number when setting function from Table 4.
When setting function from Table 5.
- When setting function for an indoor unit in an independent system, set the unit number to 01.
- When setting function for a simultaneous-Twin Triple quadruple indoor unit system, assign unit numbers from 01 to 04 to
  each indoor unit.
- When setting the same functions for an entire simultaneous Twin Triple quadruple-indoor unit system, assign “07” as 
  the unit number.

 Selecting the mode number

    Select from Table 4 and Table 5.

 Selecting the setting number.

Wireless Remote Controller Kit

for Ceiling Suspended models

PAR-SL94B-E

Summary of Contents for PAR-SL94B-E

Page 1: ...systems per group One or more wireless light receivers must be installed for each refrigerant system Number of units controlled Adapter wiring 9 wire cord standard accessory with connector is connected to the connector CN90 on the indoor unit control board Light receiver range 7m or less at within 45 degrees to the front of receiver the range varies with conditions Operating conditions Temperature...

Page 2: ...the grille Remove the screw holding the side panel and then slide the side panel forward to remove it Side panel Slide forward Catach retaining the intake grille Remove the screw holding the side panel Removing the existing brand label case Remove the brand label case name plate with MITSUBISHI ELECTRIC from the bottom right of the unit If it is difficult to remove the case use a flat blade screwd...

Page 3: ...sert the remote control into the holder Push the remote control against the wall Removing remote control Ɣ Pull the top of remote control forward NOTE The remote signal will reach the receiver over a distance of approx 7m in a straight line and approx 45 left or right If the infrared receiver is affected by fluorescent light especially inverter type it may not be able to receive the signal Take th...

Page 4: ...O STOP AUTO START h min RESET SET CLOCK MODEL SELECT The positions of the connectors may be different according to the model Please refer to the wiring diagram to confirm the positions of the connectors Test Run Measure an impedance between the power supply terminal block on the outdoor unit and the ground with a 500V Megger and check that it is equal to or greater than 1 0 M Turn on the main powe...

Page 5: ...d by the unit is entered 3 beeps 3 beeps of 0 4 seconds duration will be heard Reenter the mode number selecting If the signal was not received by the sensor or an error occurred during transmission you will not hear a beep or a double beep may be heard Press the button again Selecting the setting number Use the and buttons to change the LOSSNAY connectivity setting to 02 Direct the wireless remot...

Page 6: ...he function that can be set for the indoor unit Table 4 Itemized functions of the entire refrigerant system select unit number 00 Mode Settings Not available Available Approximately 4 minutes wait period after power is restored Indoor unit operating average Set by indoor unit s remote controller Remote controller s internal sensor Not supported Supported indoor unit is not equipped with outdoor ai...

Page 7: ...p Beep Beep Beep Off Approx 2 5 sec On 0 5 sec On 0 5 sec On 0 5 sec On 0 5 sec Off Approx 2 5 sec On 0 5 sec On 0 5 sec Repeated Number of blinks beeps in pattern indicates the check code in the following table i e n 5 for P5 Number of blinks beeps in pattern indicates the check code in the following table nth 1st 2nd 3rd 1st 2nd Self check starts Start signal received Beeper sounds Ɣ Refer to th...

Page 8: ...U7 U9 UH Others Other errors Refer to the technical manual for the outdoor unit For details check the LED display of the outdoor controller board Compressor overcurrent interruption On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code display in the LCD Wired remote controller Check code CITY ...

Reviews: