29
9-7. TEST POINT DIAGRAM
Indoor controller board
PCA-A24KA7.TH PCA-A30KA7.TH PCA-A36KA7.TH PCA-A42KA7.TH
CN3C
Transmission (Indoor/outdoor)
(0–24 V DC)
SW2
Capacity setting
SW1
Model selection
CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
CN90
Connect to the IR wireless
remote controller board (CNB)
CN20
Room temperature
thermistor (TH1)
CN22
Connect to the terminal block (TB5)
(Remote controller connecting wire)
(10.4–14.6 V DC)
LED2
Power supply (R.B)
LED1
Power supply (I.B)
LED3
Transmission
(Indoor/outdoor)
CNP
Drain-pump output (DP)
(208/230 V AC) (option)
CN01
Connect to the Terminal Block
(TB4)
(Indoor/outdoor connecting line)
Between
3
and
5
208/230 V AC
CNV
Vane motor output (MV)
12 V pulse output
SWE
Emergency operation
Jumper wire J41,J42
Pair No. setting for IR wireless
remote controller
FUSE
6.3 A , 250 V
CNMF
Fan motor
1
–
4
: 294–325 V DC
5
–
4
: 15 V DC
V
CC
: Voltage between pins of
C955 15 V DC
(Same as
5
(+)–
4
(
í
) of CNMF)
CN44
Pipe temperature
thermistor–
1
–
2
: Liquid (TH2)
3
–
4
: Cond./Eva. (TH5)
CN4F
Drain float switch (FS)
(option)
CN51
Centrally control
1
–
2
: Control signal
13 V DC pulse input (
1
: +)
3
–
4
: Operation indicator
13 V DC (
3
: +)
3
–
5
: Malfunction indicator
13 V DC (
3
: +)
CN4Y
i-See sensor (option)
CN24
Connector (Back-up heating)
CN6Y
sensor motor (option)
CN105
OCH638