31
10
FUNCTION SETTING
10-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set as necessary using the remote controller. The setting of function for each unit can only be
done by the remote controller.
(1) Functions available when setting the unit number to 00
Refer to the service manual that comes with each outdoor unit.
(2) Functions available when setting the unit number to 01–03 or AL (07 in case of wireless remote controller)
Function
Settings
Mode No.
Setting
No.
Initial setting
Setting
Filter sign
100 Hr
07
1
2500 Hr
2
ż
No
¿
lter sign indicator
3
Fan speed
Silent
08
1
Standard
2
ż
High ceiling
3
Up/down vane setting
No vanes
11
1
Equipped with vanes (vanes angle setup
1
)
2
ż
Equipped with vanes (vanes angle setup
2
)
3
OCH638