System constraint
· This function is available only in cooling mode.
11-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller. (Maintenance monitor)
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
NOTE
Setting No.
(Request code)
Setting contents
Initial
setting
No.1
(310)
Monitoring the request code of current setting
No.2
(311)
Rotation and Back-up OFF (Normal group control operation)
No.3
(312)
Back-up function only
No.4
(313)
Rotation ON (Alternating interval
1day) and back up function
No.5
(314)
Rotation ON (Alternating interval
3day) and back up function
No.6
(315)
Rotation ON (Alternating interval
5day) and back up function
No.7
(316)
Rotation ON (Alternating interval
7day) and back up function
No.8
(317)
Rotation ON (Alternating interval
14day) and back up function
No.9
(318)
Rotation ON (Alternating interval
28day) and back up function
(1) Request Code List
Rotation setting
2
nd stage cut-in setting
Ex.) Set temp. by R/C
68°F [20
:
]
Set point
79°F [26
:
]
When request code number is “323”.
79°F
2nd unit Cut-in
7.2°F
71.5°F
2nd unit Cut-out
68°F
[2nd stage cut-in function]··· Request code number "322–324"
Start operation
Sub unit start operation
Room temp.
]
Set point
Sub unit stop
Run
Stop
Stop
Run
Main
unit
IC-1
Sub
unit
IC-2
Room temp. < Set point
í
7.2°F [
í
4
:
]
[20
:
]
[22
:
]
[4
:
]
[26
:
]
Setting No.
(Request code)
Setting contents
Initial
setting
No.1
(320)
Monitoring the request code of current setting
No.2
(321)
Cut-in function OFF
No.3
(322)
Cut-in Function ON(Set point
Set temp.+ 7.2°F [4°C])
No.4
(323)
Cut-in Function ON(Set point
Set temp.+ 10.8°F [6°C])
No.5
(324)
Cut-in Function ON(Set point
Set temp.+ 14.4°F [8°C])
OCH638