1. Specifications
1-1.Main Features
1
(1) List of Models
<10HP System>
<20HP System>
PUD-P250YMF-C
10HP(Down flow): PFD-P250VM-A(-H)
20HP(Down flow): PFD-P500VM-A(-H)
✻
'-H' in the indoor units indicates that the unit pipes come out of the top of the unit (50/60Hz, fit to order).
✻
PFD-type indoor units cannot be connected to outdoor units other than the ones specified above.
✻
PFD-type indoor units and other types of indoor units cannot coexist in the same refrigerant system.
When using a PFD-P500VM-A as an indoor unit, connect 2 PUD-P250YMF-C outdoor units to each
indoor unit and operate with a built-in remote control for the indoor unit.
✻
1: Bold line indicates refrigerant piping (gas/liquid). This system consists of 2 refrigerant circuits.
✻
2: Indicates TB3-type transmission line that connects the indoor and outdoor units.
This system consists of 2 refrigerant circuits.
✻
3: Indicates TB7-type transmission line that allows the unit to communicate with the controller.
When using a PFD-P250VM-A as an indoor unit, connect an outdoor unit PUD-P250YMF-C to each
indoor unit and operate with a built-in remote control for the indoor unit.
✻
1: Bold line indicates refrigerant piping (gas/liquid). This system consists of one refrigerant circuit.
✻
2: Indicates TB3-type transmission line that connects the indoor and outdoor units.
This system consists of 1 refrigerant circuit.
✻
3: Indicates TB7-Type transmission line that allows the unit to communicate with the controller.
} Outdoor Unit
} Indoor Unit
Outdoor Unit
G-50A
PUD-P250YMF-C
Indoor Unit
PFD-P250VM-A
TB7 TB3
✻
2
✻
3
✻
1
12V DC
M-NET
PAC-SC50KUA
UP
POWER RATING
MODEL
WEIGHT
SERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA
Outdoor Unit
PUD-P250YMF-C
Indoor Unit
PFD-P500VM-A
TB7
TB3
✻
2
✻
1
TB3
PUD-P250YMF-C
TB7
✻
3
G-50A
12V DC
M-NET
PAC-SC50KUA
UP
POWER RATING
MODEL
WEIGHT
SERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA