13
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
(80°F) W.B. 19
(66°F)
Outdoor : D.B. 35
(95°F) W.B. 24
(75°F)
Heating Indoor : D.B. 20
(68°F)
Outdoor : D.B. 7
(45°F)
W.B. 6
(43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35°C, W.B. 22.5°C D.B. 46°C
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C
+
1
Heating
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit D.B. 17°C
D.B. -20°C, W.B. -20°C
4. Above data are based on the indicated voltage.
+
1. If optional air protect guide is installed : D.B.-15
Indoor unit
3 phase 400V 50Hz
3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
342~457V, 50Hz
Model name
Indoor unit
PEA-RP200GA
PEA-RP250GA
Outdoor unit
PUHZ-RP200YKA
PUHZ-RP250YKA
Cooling
Capacity
Btu/h
65,000
75,000
kW
19.0(9.0-22.4)
22.0(11.2-28.0)
Total input
kW
6.70
8.34
EER
Energy label class
2.84
2.64
-
-
SHF
0.81
0.86
Heating
Capacity
Btu/h
76,400
92,000
kW
22.4(9.5-25.0)
27.0(12.5-31.5)
Total input
kW
6.50
8.20
COP
3.45
3.29
Energy label class
-
-
Booster heater
kW
-
-
Power supply
Phase
:
3
Cycle
Hz
50
Voltage
V
400
Breaker size
A
Indoor 15 / Outdoor 32
Indoor unit
Air flow
CMM
52-65
64-80
(Low-High)
CFM
1835-2295
2260-2825
External pressure
Pa
150
Sound level
dB(A)
48-51
49-52
(Low-High)
External finish
Galvanized steel
Dimension
W : mm
1600
1400
D : mm
634
H : mm
400
W : inch
63
55-1/8
D : inch
25
H : inch
15-3/4
Weight
kg
70
77
lbs
155
170
Unit drain pipe
R1
Outdoor unit
Air flow
CMM
140
CFM
4,940
Sound level at cooling
dB(A)
58
Sound level at heating
dB(A)
59
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
1,050
D : mm
330+30
H : mm
1,338
W : inch
41-5/16
D : inch
13 + 1-3/16
H : inch
52-11/16
Weight
kg
135
lbs
297
141
311
Refrigerant pipe size
Gas side O.D.
mm
25.4
inch
1
Liquid side O.D.
mm
12.7
inch
1/2
9.52
3/8
Refrigerant pipe length
Height difference
m
Max. 30
Length
m
Max. 100