75
9
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP71BA2
PLA-RP100BA
PLA-RP100BA3
PLA-RP125BA
PLA-RP125BA2
PLA-RP140BA2
Airfl ow
m
3
/min.
15
18
18
21
30
31
32
Air speed
m/sec.
2.6
3.2
3.2
3.7
5.3
5.4
5.6
Coverage range
m
4.1
4.8
4.8
5.6
8.0
8.2
8.5
PCA-RP50KA
PCA-RP60KA
PCA-RP71KA
PCA-RP100KA
PCA-RP125KA
PCA-RP140KA
Airfl ow
m
3
/min.
15
19
20
28
29
32
Air speed
m/sec.
3.3
3.1
3.2
3.6
3.7
4.1
Coverage range
m
9.0
9.6
10.1
12.5
12.9
14.2
PCA-RP71HA
PCA-RP125HA
Airfl ow
m
3
/min.
19
38
Air speed
m/sec.
2.9
4.2
Coverage range
m
7.9
13.2
PKA-RP35HAL
PKA-RP50HAL
Airfl ow
m
3
/min.
12
12
Air speed
m/sec.
6.1
6.1
Coverage range
m(ft)
10.8(35.4)
10.8(35.4)
PKA-RP60KAL
PKA-RP71KAL
PKA-RP100KAL
Airfl ow
m
3
/min.
22
22
26
Air speed
m/sec.
6.0
6.0
6.8
Coverage range
m(ft)
14.3(46.9)
14.3(46.9)
16.1(52.8)
PSA-RP71GA
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
Airfl ow
m
3
/min.
18
31
33
35
Air speed
m/sec.
2.6
4.5
4.8
4.9
Coverage range
m
8.3
14.3
15.2
16.1
w
The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.