background image

WT03272X02

Printed in Japan

HEAD OFFICE MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX J24532 CABLE MELCO TOKYO

Please be sure to put the contact address/telephone number on

this manual before handing it to the customer.

The product at hand is

based on the following

EU regulations:

Low Voltage Directive 73/23/EEC

Electromagnetic Compatibility Directive 89/

336/EEC

This product is designed and intended for use in the residential, commer-

cial and light-industrial environment.

Summary of Contents for PLFY-P-VLMD-A

Page 1: ...leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XE...

Page 2: ...2 9 mounting hole G 4 ø2 9 mounting hole 3 2 Fig 3 2 1 H D 630 E 550 40 40 D A E B 102 102 A A B B C F B A D 50 10 G C A Nut B Washer supplied with the unit body C Hanging bolt ø10 M10 screw D Ceiling hole dimensions E Hanging bolt pitch F Hanging bolt G Finished ceiling surface H Hanging bracket A D C B A Drain pipe side B Unit body C Packing cap D Lifting machine B A B Indoor unit s bottom surfa...

Page 3: ...INNER F Unit body G Provided flare insulation 2 A Tape 3 B Fasten with tape C Provided tie band 4 figure showing the flare insulation D I C H G K I J 3 C 30 cm G Drain hose Accessory s s s s s Be sure to use the supplied drain hose Accessory H Less than 300 mm I Hard vinyl chloride 90 elbow field supply J Hard vinyl chloride VP 25 field supply K Tie band small Accessory D D D E F 2 D Indoor unit E...

Page 4: ...ON SW14 N0 N0 W254613G03 FP AD P JP2 JP3 JP4 CN82 8 1 6 1 10 1 240V 220V SW5 JP1 SWC SWA 1 3 2 0 SW12 10 0 SW11 1 0 Address board Fig 8 2 5 G I J J J K K K F J J L K H 1 3 L1 L2 L4 l L3 2 G Outdoor unit H Earth I BC controller J Indoor unit K Remote controller L Non polarized 2 wire Fig 8 2 1 A A C TB5 TB5 S M1M2 S M1M2 C B TB3 M1M2 A A C TB5 TB15 TB5 TB15 S M1M2 S M1M2 B TB3 M1M2 2 1 C 2 1 Fig 8 ...

Page 5: ...y limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is install...

Page 6: ...eteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base vacuum gauge refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R407C the refrigerant may deteriorated If water is mixed in the R407C the refrigerator oil may deteriora...

Page 7: ...the back surface of each split flow duct end connection is insulating material Use a cutter knife to cut the insulating material along the end connection To adjust the fresh air intake capacity cut the two places as shown in the figure at right and rotate the intake 3 3 Combining indoor units with outdoor units For combining indoor units with outdoor units refer to the outdoor unit installation ma...

Page 8: ... Packing cap D Lifting machine Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and humidity it is necessary to use pipe size and insulating material s thickness more than those given in the table above 3 If there are customer s specificati...

Page 9: ...e the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil et...

Page 10: ...cc D Water E Filling port Building clinic hospital or communications station without noise supposedly generated from inverter equipment private power gen erator high frequency medical equipment radio used communications equipment and so on Residence or independent store without noise Facility example for noise judgment All facilities VCTF VCTFK CVV CVS VVR VVF VCT or shielding wire CVVS or CPEVS S...

Page 11: ...ol board to ON The setting of SW1 7 and SW1 8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF 8 2 Connecting remote controller indoor and outdoor transmission cables Remote contoroller is optionally available Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For specific...

Page 12: ...t the contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: