–31–
Outdoor unit capacity is displayed as function code.
Model name
function code
PUH-P8MYA
20
PUH-P10MYA
25
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
When there are no indoor units, “00” is displayed.
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
When there are no indoor units, “00” is displayed.
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
When there are no indoor units, “00” is displayed.
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
When there are no indoor units, “00” is displayed.
8 - 39.5
When there are no indoor units, “00” is displayed.
17 - 30
When there are no indoor units, “00” is displayed.
Outdoor unit set
information 1
Outdoor unit set
information 2
Indoor unit piping
temperature (TH2)
Indoor 1
–39 - 88
Indoor unit piping
temperature (TH2)
Indoor 2
–39 - 88
Indoor unit piping
temperature (TH2)
Indoor 3
–39 - 88
Indoor unit piping
temperature (TH2)
Indoor 4
–39 - 88
Indoor intake tem-
perature
8 - 39.5
Indoor set temperature
17 - 30
Code display
Code display
°
C
°
C
°
C
°
C
°
C
°
C
SW2 setting
Display contents
Description of display
Unit
Outdoor unit set information 1
Function setting (display valves)
3-phase power source detection Do
(1) Do not
(0)
Cooling only switching
Cooling only
(2) H/P
(0)
Night mode
Night mode
(1) Normal mode
(0)
Defrosting end time
12
°
C continuous 2 minutes (2) 8
°
C continuous 2 minutes (0)
Defrosting prohibit time
Fixed
(4) Training
(0)
Tens digit
Units digit
Set information display values are added and displayed at each position.
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF