–32–
Indoor unit control
status
Indoor 1, 2
Indoor unit control
status
Indoor 3, 4
Condenser/evaporater
temperature (TH3)
Outdoor unit control
status
Discharge super heat
SHd
0 - 216
Cooling: Outdoor TH2 -
Outdoor TH3
Heating: Outdoor TH2
- Indoor TH3
(Average)
Sub cool Sc
0 - 130
Cooling: Outdoor TH3
- Outdoor
TH1
Heating: Indoor TH3
(Average) -
Indoor TH2
(Average)
Target sub cool step N
1 - 5
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
<Example> When –10,
every other second
–
←→
–10
0 - 216
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 150,
every other second
1
←→
50
0 - 130
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
1
←→
00
1 - 5
–
–
°
C
–
°
C
°
C
–
SW2 setting
Display contents
Description of display
Unit
Indoor unit No.1
Indoor unit No.3
Indoor unit No.2
Indoor unit No.4
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
—
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
Display
0
1
2
3
4
5
6
7
Outdoor unit
←
←
←
←
←
←
←
←
Control mode display system
Indoor unit No.1
Indoor unit No.3 Outdoor unit
Indoor unit No.2
Indoor unit No.4
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
—
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
Display
0
1
2
3
4
5
6
7
Outdoor unit
←
←
←
←
←
←
←
←
Control mode display system
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF