–41–
Start
Piping work complete?
Turn on indoor power *1
Check that mains power is OFF
Turn on mains power
Turn on emergency operation switch
(SWE) on indoor controller board
Short CN31 (emergency operation
connector) on outdoor controller board
Check that emergency operation starts,
and that operation mode display flashes
Set operation mode (cooling or heating) with SW4-2 on outdoor board
(SW4-1 not used)
SW4
Cooling
Heating
OFF ON
1
2
NO
YES
4) Emergency operation method
* Before starting, recheck that the trouble allows
emergency operation.
*1 Only when PEH-P8MYA or P10MYA indoor unit
connected.
*1. When PEH-P8MYA or P10MYA indoor unit is
connected, first turn off the outdoor unit power,
then turn off the indoor unit power.
5) Emergency operation release method
Turn off mains power. (Outdoor, indoor)
*1
a)
Turn on mains power
e)
Turn off emergency operation switch
(SWE) on indoor controller board
b)
Open CN31 (emergency operation
connector) on outdoor controller board
c)
SW4
OFF ON
1
2
Set SW4-2 as shown below
d)