From the previous page.
Error Code
Meaning of error code and detection method
Case
Judgment and action
A7
(6607)
5. If displayed address or attribute is
FRESH MASTER,
Indoor unit detects abnormality when
indoor unit transmits signal to FRESH
MASTER and there was no reply (ACK).
1
During sequential operation of
indoor unit and FRESH MAS-
TER of other refrigerant sys-
tem, if indoor unit transmits
signal to FRESH MASTER
while outdoor unit power sup-
ply of same refrigerant system
with FRESH MASTER is put
off or within two minutes of
restart, abnormality is detect-
ed.
2
Contact failure of transmission
wire of indoor unit or FRESH
MASTER
3
Disconnection of transmission
connector (CN2M) of indoor
unit or FRESH MASTER
4
Defective transmitting receiv-
ing circuit of indoor unit or
FRESH MASTER
6. If displayed address or attribute is
LOSSNAY,
Indoor unit detects abnormality when
indoor unit transmits signal to LOSSNAY
and there was no reply (ACK).
1
If the power supply of LOSS-
NAY is off, indoor unit detects
abnormality when it transmits
signal to LOSSNAY.
2
During sequential operation of
indoor unit and LOSSNAY of
other refrigerant system, if
indoor unit transmits signal to
LOSSNAY while outdoor unit
power supply of same refriger-
ant system with LOSSNAY is
put off or within 2 minutes of
restart, abnormality is detect-
ed.
3
Contact failure of transmission
wire of indoor unit of LOSS-
NAY
4
Disconnection of transmission
connector (CN2M) of indoor
unit
5
Defective transmitting receiv-
ing circuit of indoor unit or
LOSSNAY
7. If displayed address or attribute is
nonexistent.
1
The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2
Abnormality is detected when
indoor unit transmits signal
because the address of
FRESH MASTER and LOSS-
NAY are changed after
sequential operation of
FRESH MASTER and LOSS-
NAY by remote controller.
4. If displayed address or attribute is
remote controller,
Indoor unit detects abnormality when
indoor unit transmits signal to remote
controller and there was no reply (ACK).
1
During group operation with
indoor unit of multi- refrigerant
system, if indoor unit transmit
to remote controller while out-
door unit power supply of one
refrigerant system is put off or
within two minutes of restart,
abnormality is detected.
2
Contact failure of transmission
wire of remote controller or
indoor unit
3
Disconnection of transmission
connector (CN2M) of indoor
unit
4
Defective transmitting receiv-
ing circuit of indoor unit or
remote controller
Same as mentioned in “A7” of the previous
page.
OC338C-2.qxp 07.5.24 11:29 AM Page 36