49
<Output pulse signal and the valve operation>
(2) Linear expansion valve operation
A
B
C
Open
Extra tightning (about 32 pulse)
Pulse number
500 pulse
Opening a valve
all the way
Close
V
alve position (capacity)
Opening a valve : 8
→
7
→
6
→
5
→
4
→
3
→
2
→
1
→
8
Closing a valve : 1
→
2
→
3
→
4
→
5
→
6
→
7
→
8
→
1
The output pulse shifts in above order.
•. When linear expansion valve operation stops, all output phase
become OFF.
• When the switch is turned on, 700 pulse closing valve signal will
be sent till it goes to
A
point in order to define the valve position.
(The pulse signal is being sent for about 20 seconds.)
• When the valve moves smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the
pulse number moves from
B
to
A
or when the valve is locked,
more noise can be heard than normal situation.
No noise is heard when the pulse number moves from
B
to
A
in
case coil is burn out or motor is locked by open-phase.
• Noise can be detected by placing the ear against the screw dri-
ver handle while putting the screw driver to the linear expansion
valve.
LEV
M
1
6
[
4
[
4
[
3
[
2
[
1
2
1
Red
Brown
Blue
Orange
Yellow
White
3
4
5
6
Connector LEV-A
DC12V
Outdoor controller board
Drive circuit
[
3
[
2
[
1
3
2
5
4
Linear expansion valve
(1) Operation summary of the linear expansion valve
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller circuit board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller circuit board and the linear expansion valve>
1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
[
1
Output
(Phase)
Output
[
2
[
3
[
4
2
3
4
5
6
7
8
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OC338C-2.qxp 07.5.24 11:29 AM Page 49