8
OCH721A
5-1. REFILLING REFRIGERANT CHARGE (R410A: oz, kg)
Service Ref.
Piping length (one way)
PUZ-HA24NHA
50 ft
60 ft
70 ft
80 ft
90 ft
100 ft 110 ft 120 ft 130 ft 140 ft 150 ft 160 ft 165 ft
Factory
charged
15 m
18 m
21 m
24 m
27 m
30 m
34 m
37 m
40 m
43 m
46 m
49 m
50 m
123 oz 123 oz 123 oz 130 oz 137 oz 144 oz 151 oz 158 oz 165 oz 172 oz 179 oz 186 oz 190 oz
123 oz
3.5 kg 3.5 kg 3.5 kg 3.7 kg 3.9 kg 4.1 kg 4.3 kg 4.5 kg 4.7 kg 4.9 kg 5.1 kg 5.3 kg 5.4 kg
3.5 kg
5-2. COMPRESSOR TECHNICAL DATA
(Winding resistance at 68°F [20°C])
Service Ref.
PUZ-HA24NHA
Compressor model
DNB28FBAMT
Winding resistance
(Ω)
U-V
0.74
U-W
0.74
W-V
0.74
5
DATA
5-3. NOISE CRITERION CURVES
PUZ-HA24NHA
10
20
30
40
50
60
70
80
90
63
125
250
500
1000
2000
4000
8000
COOLING
MODE
HEATING
52
SPL(dB)
53
LINE
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
5 ft
3.3 ft
MICROPHONE
UNIT
GROUND
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
Additional charge is required for pipes longer than 70 ft.