9 - 8 9 - 8
MELSEC
9 UTILITY OPERATIONS
9.2.4 Routing Parameter Setting screen operation
The routing parameter setting screen is used to set the transfer destination, relay
destination network number, and relay destination station number.
POINT
(1) The routing parameters are common with channels No. 51 to 54.
They cannot be set one channel No. at a time.
(2) Up to 64 routine parameters can be set.
Item Content
No.
Input the number of the line to set or change. (Setting range : 1 to 64)
Transfer to Network No.
Input the transfer destination network number
Intermediate Network No.
Input the relay destination network number
Intermediate Sta. No.
Input the relay destination station number.
Set button
Enters the data that has been set in Set data.
Setting Data
Displays a list of data that has been set so far.
Change button
Selecting a line to be changed and clicking the button will change the entered set data.
(Double-clicking the line to be changed also does the same operation.)
Delete button
Selecting a line to delete and clicking the button will delete the entered set data.
Channel
Selects the channel No. where the settings are to be changed for the network
configuration.
If MELSECNET/10 does not exist on the routing path, select "Composition without
MELSECNET/10 network"
1
.
1: If a MELSECNET/10 board exists in the network, do not select the checkbox.
Due to the maximum transmitted data size (1920 byte for the configuration which
is not including MELSECNET/10 and 960 byte for the configuration which is
including MELSECNET/10) differs depending on the network system
configuration, the data will be missed at transmission via MELSECNET/10.
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......