12 - 15 12 - 15
MELSEC
12 APPLICATION FUNCTIONS
(2) Routing parameter settings
(a) Setting screen
A maximum of 64 "Transfer to Network No." can be set on the "Routing
Parameter Setting" of the MNETH utility.
Note that the same Transfer to network number cannot be designated more
than once (multiple). Therefore, the host can become the request source or
can be accessed to other station through the host with 64 types of different
"Transfer to Network No."
Setting item
Valid setting range
Transfer to Network No.
1 to 239
Intermediate Network No.
1 to 239
Intermediate Station No.
1 to 64
(b) Setting method
Set the routing parameters according to the procedure described below.
Request
source
Network No.
Relay station
Network No.
To access "network No. ," it is necessary to route through station No. of network No. .
Transfer
to
network No.
1
2
Request
destination
Intermediate
network No.
Intermediate
station No.
Summary of Contents for Q80BD-J71BR11