14 TROUBLESHOOTING
14.3.2 Checking on Event Viewer screen
Event logs related to the MELSECNET/H board are displayed as "AMneth" in the
Source field on the "Event Viewer" screen.
The following table lists the errors displayed in the event viewer viewer.
Event ID
(0 to FFFF
H
)
Error content
Corrective action
0 (0
H
)
Failed to start the MELSEC network service.
Failed to register the main thread of service, or failed to set
the service status.
Restart the PC. If the error persists, reinstall
Windows
R
.
257 (101
H
)
The MELSECNET/H board is not loaded, or the I/O address is
overlapping with other hardware.
Change the I/O address setting for the
MELSECNET/H board or other hardware.
1
258 (102
H
)
No response from hardware.
Replace the MELSECNET/H board.
259 (103
H
)
The number of MELSECNET/H boards detected exceeds the
maximum number that can be loaded.
Remove MELSECNET/H boards until the number
falls within the maximum limit
260 (104
H
)
The board conflicts with other device.
Check for overlapping setting with other optional
board.
261 (105
H
)
An attempt to create a device object has failed.
Increase the system memory.
262 (106
H
)
An attempt to link the device name has failed.
Reinstall Windows
R
.
263 (107
H
)
An attempt to secure dual-port memory has failed.
Check for overlapping setting with other optional
board.
264 (108
H
)
An attempt to perform interrupt registration has failed.
265 (109
H
)
An error occurred when reading I/O.
Replace the MELSECNET/H board.
266 (10A
H
)
An error occurred when writing I/O.
267 (10B
H
)
An error occurred during memory transfer.
Reinstall Windows
R
.
268 (10C
H
)
An error occurred during receiving process.
——
269 (10D
H
)
An error occurred during sending process.
——
270 (10E
H
)
An error occurred during interrupt process.
Reinstall Windows
R
.
271 (10F
H
)
An error occurred during UNLOAD process.
272 (110
H
)
An error occurred during StartIo process.
273 (111
H
)
An error occurred during critical session.
274 (112
H
)
An error occurred during IoTimer process.
275 (113
H
)
An error occurred during IoCompletion process.
276 (114
H
)
An error occurred during DPC process.
277 (115
H
)
An error occurred when opening registry database.
278 (116
H
)
An error occurred when reading from registry database.
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......