App - 9 App - 9
MELSEC
APPENDIX
Set the parameters
Set the parameters recorded before the replacement.
• • • Chapter 7 PARAMETER SETTINGS
↓
Check the network
Test the cable connection and data link on the network.
• • • Section 6.5 Test
↓
Execute a user program
Execute a user program or utility.
↓
Operation
(2) Precautions
When a MELSECNET/H board is replaced, channel numbers are automatically
re-assigned. For details on the channel number to be assigned, refer to Section
6.3.4.
As parameter settings (Refer to Chapter 7) correspond to channel numbers, the
replaced board works with the parameter settings shown below.
When un-used channel numbers are newly assigned:
Works with the default status.
When channel numbers that were used are assigned:
Works with the parameter settings corresponding to the channel
numbers.
When replacing a MELSECNET/H board, check the parameter settings with the
“Board information setting” screen.