Appendix 9.2 Behavior when the fast startup function is enabled
(1) Target operating system
The following operating systems have the fast startup function.
Windows 10
Windows 8.1, Windows Server 2012 R2
Windows 8, Windows Server 2012
(2) Behavior when the fast startup function is enabled
The following explains the behavior of the board when the fast startup function is
enabled.
The board is not reconnected even after the fast startup.
After the fast startup, "-28141(9213H) : System sleep error" occurs when
accessing MELSECNET/H board from the MELSECNET/H utility or an
application program, which includes MELSEC data link library function.
(3) Countermeasure
When the fast startup function is enabled, the setting is changed to disabled by
MELSECPowerManager.
For details of MELSECPowerManager, refer to Appendix 10.