3 - 1 3 - 1
MELSEC
3 SPECIFICATIONS
3 SPECIFICATIONS
This section explains the MELSECNET/H board general specifications, performance
specifications.
3.1 General Specifications
This section explains the MELSECNET/H board general specifications.
Item Specifications
Operating ambient temperature
0 to 55
°
C
Storage ambient temperature
-25 to 75
°
C
Operating ambient humidity
Storage ambient humidity
5 to 95 % RH, non-condensing
Under intermittent vibration
Frequency
Constant
acceleration
Half
amplitude
Sweep count
5 to 8.4 Hz
—
3.5 mm
8.4 to 150 Hz
9.8m/s
2
—
10 times each in
X, Y and Z
directions
Under continuous vibration
Frequency
Constant
acceleration
Half
amplitude
Sweep count
5 to 8.4 Hz
—
1.75 mm
Vibration resistance
Compliant with
JIS B 3502 and
IEC 61131-2
8.4 to 150 Hz
4.9m/s
2
—
—
Shock resistance
Compliant with JIS B 3502
and
IEC 61131-2 (147 m/s
2
, 3 times each in X, Y, and Z directions)
Operating atmosphere
i
t
No corrosive gases
Operating altitude
1
0 to 2000 m
Installation location
Inside a control panel
Over-voltage category
2
II or less
Pollution rate
3
2 or less
1: Do not use or store the board under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause a malfunction.
2: This indicates the section of the power supply to which the equipment is assumed to be connected
between the public electrical power distribution network and the machinery within the premises. Category
II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage
withstand level for up to the rated voltage of 300 V is 2500 V.
3: This index indicates the degree to which conductive material is generated in terms of the environment in
which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary
conductivity caused by condensation must be expected occasionally.
REMARK
General specifications both MELSECNET/H board and a personal computer must
be satisfied after installation.
3
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......