5 - 2 5 - 2
MELSEC
5 EMC AND LOW VOLTAGE DIRECTIVE
5.1.1 EMC Directive related standards
The standards applicable to the EMC Directive are listed below.
All test items were tested by installing each device on a personal computer bearing a
CE certification logo.
(1) Emission requirements
Standard
Test item
Test description
Value specified in standard
EN61131-2 :
2007
CISPR16-2-3
Radiated emission
1
The electromagnetic wave
which the product emits to the
external space is measured.
• 30M-230MHz
QP: 40dB V/m (10m in measurement range)
2
• 230M-1000MHz
QP: 47dB V/m (10m in measurement range)
CISPR16-2-1,
CISPR16-1-2
Conducted emission
1
The noise level which the
product emits to the power line
is measured.
• 0.15 to 0.5MHz, QP: 79dB, Mean: 66dB
2
• 0.5 to 30MHz, QP: 73dB, Mean: 60dB
1: The tests were conducted installed in a control panel.
2: QP: Quasi-peak value, Mean: Average value
(2) Immunity requirements
Standard
Test item
Test description
Value specified in standard
EN61131-2 :
2007
EN61000-4-2
Electrostatic discharge
immunity
1
An electrostatic discharge is
applied to the enclosure of the
equipment.
• 8kV Air discharge
• 4kV Contact discharge
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field
immunity
1
An electric field is radiated to
the product.
80% AM modulation@1kHz
• 80 to 1000MHz: 10V/m
• 1.4 to 2.0GHz: 3V/m
• 2.0 to 2.7GHz: 1V/m
EN61000-4-4
Fast transient burst
immunity
1
Burst noise is applied to power
lines and signal lines.
• AC/DC power, I/O power, and
AC I/O (unshielded) lines: 2kV
• DC I/O, analog, and communication lines: 1kV
EN61000-4-5
Surge immunity
1
Lightning surge is applied to
power lines and signal lines.
• AC power, AC I/O power, and
AC I/O (unshielded) lines: 2kV CM, 1kV DM
• DC power and DC I/O power lines:
0.5kV CM, 0.5kV DM
• DC I/O, AC I/O (shielded), analog,
communication: 1kV CM
EN61000-4-6
Conducted RF immunity
1
High-frequency noise is applied
to power lines and signal lines.
0.15 to 80MHz, 80% AM modulation @1kHz,
10Vrms
EN61000-4-8
Power-frequency magnetic
field immunity
1
The product is immersed in the
magnetic field of an induction
coil.
50Hz/60Hz, 30A/m
EN61000-4-11
Voltage dips and
interruption immunity
1
Power voltage is momentarily
interrupted.
• 0%, 0.5 period, starting at zero-crossing
• 0%, 250/300 period (50/60Hz)
• 40%, 10/12 period (50/60Hz)
• 70%, 25/30 period (50/60Hz)
1: The tests were conducted installed in a control panel.
5
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......