6 - 12 6 - 12
MELSEC
6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION
6.4.1 Optical loop system
The precautions for connecting the optical fiber cable with Q80BD-J71LP21-25,
Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G and Q80BD-
J71LP21GE in an optical loop system are given below.
(1) Precautions for connecting
(a) The types of optical fiber cables that can be used vary depending on the
distance between stations.
Distance between stations (m)
Q80BD-J71LP21-25,
Q81BD-J71LP21-25,
Q80BD-J71LP21S-25
Type
10Mbps 25Mbps
Q80BD-J71LP21G
10Mbps (fixed)
Q80BD-J71LP21GE
10Mbps (fixed)
L type
500 (1640.5 ft.)
200 (656.2 ft.)
SI type optical fiber cable
(Old type: A-2P- )
H type
300 (984.3 ft.)
100 (328.1 ft.)
SI optical fiber cable
500 (1640.5 ft.)
200 (656.2 ft.)
H-PCF optical fiber cable
1000 (3281 ft.) 400
(1312.4 ft.)
Broad-band H-PCF optical fiber cable 1000
(3281 ft.)
1000 (3281 ft.)
QSI optical fiber cable
1000 (3281 ft.)
1000 (3281 ft.)
Not allowed
GI optical fiber cable 2000
(6562 ft.)
Not allowed
62.5 GI optical fiber cable
Not allowed
Not allowed
Not allowed
2000 (6562 ft.)
(b) When connecting an optical fiber cable to Q80BD-J71LP21-25, Q81BD-
J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G and Q80BD-
J71LP21GE the restrictions on the bending radius should be observed.
For bending radius details, check with the cable to use.
(c) Maintain the bending radius of the optical fiber cable within the allowable
range using a tool for securing the optical fiber cable bending radius.
This tool may be purchased from Mitsubishi Electric System Service, Inc, or
your nearest dealer. Please inquire for more information.
(d) When laying the optical-fiber cables, do not touch the fiber cores of the
cable and module connectors, and do not let dust or particles collect on
them.
If oil from hands, dust or particles adhere to the cores, the accumulated
transmission loss may cause malfunctions in the data link.
Do not detach the cover until the cable is attached.
(e) When attaching or detaching the optical fiber cable to/from the module, pull
or insert the cable by holding the cable connector securely with your hand.
(f) Connect the cable and module connectors securely until you hear a "click"
sound.
(g) When attaching or detaching the optical fiber cable to/from the module,
make sure to power off the personal computer and external power supply.
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......